Error no.
or ID
Display
0
0
0
0
0
Reserved
0
0
0
1
1
Hardware fault
0
0
1
0
2
EEROM fault
0
0
1
1
3
Internal memory error
0
1
0
0
4
Fieldbus hardware fault
0
1
0
1
5
Script error
0
1
1
0
6
Reserved
0
1
1
1
7
RS transmission buffer overflow
1
0
0
0
8
RS receiver buffer overflow
1
0
0
1
9
RS timeout
1
0
1
0
10
General fieldbus error
1
0
1
1
11
Parity error or stop bit error (frame
check)
1
1
0
0
12
Reserved
1
1
0
1
13
Fieldbus configuration error
1
1
1
0
14
Fieldbus data buffer overflow
1
1
1
1
15
Reserved
Undefined oper-
ating statuses
Battery switches off during start-up procedure:
Keep the battery switched off for at least 120 minutes and then switch it on again. If this
does not resolve the error, notify Customer Services.
Battery switched off with a SOC (state of charge) of 0%:
Communication error – Disconnect the inverter on the DC side and isolate it from the grid
on the AC side. Wait 5 minutes and then reconnect the inverter on both the DC and AC
sides. If this does not resolve the error, notify Customer Services.
Battery active, state of charge (SOC) is more than 90% and red LED is flashing:
Battery charging error – Disconnect the inverter on the DC side and isolate it from the
grid on the AC side. Wait 30 minutes and then reconnect the inverter on both the DC and
AC sides. If this does not resolve the error, notify Customer Services.
Battery not charging or discharging (SOC indicated on web interface does not
match that of the battery):
Check whether battery is switched on – If it is not, switch it on.
If it is, there is a communication error – Disconnect the inverter on the DC side and isol-
ate it from the grid on the AC side. Wait 5 minutes and then reconnect the inverter on
both the DC and AC sides. If this does not resolve the error, notify Customer Services.
Battery no longer being displayed on web interface (triangular view instead of
square view):
131
EN
Содержание Symo Hybrid 3.0-3-S
Страница 2: ......
Страница 10: ...10 ...
Страница 11: ...General information 11 ...
Страница 12: ...12 ...
Страница 16: ...16 ...
Страница 34: ...34 ...
Страница 35: ...Operation 35 ...
Страница 36: ...36 ...
Страница 66: ...66 ...
Страница 67: ...Fronius system monitoring 67 ...
Страница 68: ...68 ...
Страница 80: ...80 ...
Страница 81: ...Current data services and settings offered by Fronius system monitor ing 81 ...
Страница 82: ...82 ...
Страница 119: ...Troubleshooting and maintenance 119 ...
Страница 120: ...120 ...
Страница 133: ...Appendix 133 ...
Страница 134: ...134 ...