Code
Description
Behaviour
Remedy
314,
315
Internal system error
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
*)
318
Solar module return current detec-
ted
324
DC module overtemperature (bat-
tery)
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
Purge cooling air
openings and heat
sink; **)
*) If the status code is displayed all the time: Notify a Fronius-trained service technician.
**) Fault is rectified automatically. If this status code keeps recurring, contact your system fitter
Status codes –
Class 4
Some of the class 4 status codes necessitate intervention by a Fronius-trained service
engineer.
Code
Description
Behaviour
Remedy
401
Unable to communicate with the power
stage set
The inverter will automat-
ically attempt to connect
again and, if possible, will
resume feeding energy
into the grid.
*)
406
DC module temperature sensor faulty
(PV)
407
AC module temperature sensor faulty
408
DC component measured in the grid
too high
412
Fixed voltage mode has been selected
instead of MPP voltage mode, and the
fixed voltage has been set to too low or
too high a value.
-
**)
415
Safety cut-out via option card or
RECERBO has triggered
The inverter is not feeding
any energy into the grid.
*)
416
No communication possible between
power stage set and control system.
The inverter will automat-
ically attempt to connect
again and, if possible, will
resume feeding energy
into the grid.
*)
417
Hardware ID problem
The inverter will automat-
ically attempt to connect
again and, if possible, will
resume feeding energy
into the grid.
Update inverter firm-
ware; *)
420
Unable to communicate with system
monitoring
425
Unable to communicate with the power
stage set
426 -
427
Possible hardware fault
431,
432
Software problem
The inverter is not feeding
any energy into the grid.
Perform AC reset
(switch automatic cir-
cuit breaker off and on
again); update inverter
firmware; *)
123
EN
Содержание Symo Hybrid 3.0-3-S
Страница 2: ......
Страница 10: ...10 ...
Страница 11: ...General information 11 ...
Страница 12: ...12 ...
Страница 16: ...16 ...
Страница 34: ...34 ...
Страница 35: ...Operation 35 ...
Страница 36: ...36 ...
Страница 66: ...66 ...
Страница 67: ...Fronius system monitoring 67 ...
Страница 68: ...68 ...
Страница 80: ...80 ...
Страница 81: ...Current data services and settings offered by Fronius system monitor ing 81 ...
Страница 82: ...82 ...
Страница 119: ...Troubleshooting and maintenance 119 ...
Страница 120: ...120 ...
Страница 133: ...Appendix 133 ...
Страница 134: ...134 ...