78
Max. deviation
Used to enter a % value for how large the difference between the two average values can
be
Threshold
Used to enter a value in Ah for the average solar module string currents for the measuring
channels that will trigger a warning on the display if it is exceeded
Device Info
Used to display settings relevant to a utility company. The displayed values depend on the
respective country setup or device-specific inverter settings.
Unit %
Setting range
5 - 99
Factory setting
20
Unit Ah
Setting range
2 - 50
Factory setting
4
Display range
Setup / Version / Group / DC-Mode / FIX / User / GMTi / GMTr
/ ULL / LL Trip / UIL max / UIL min / UOL max / UOL min / FIL
max / FIL min / FOL max / FOL min / Max. P AC / GPIS / GFD-
PRv / GFDPR
Setup
Country setup
Version
Country setup version
Group
Inverter software update group
DC mode
DC operating mode
FIX
Voltage value in V for fixed voltage operation
User
Voltage value in V for MPP user operation
GMTi
Startup time of the inverter in s
GMTr
Restart time in s after a grid error
ULL
Grid voltage average value over 10 minutes in V.
LL Trip
Detection time for long-term voltage monitoring
UIL max
Upper inner grid voltage value in V
UIL min
Lower inner grid voltage value in V
UOL max
Upper outer grid voltage value in V
UOL min
Lower outer grid voltage value in V
FIL max
Upper inner grid frequency value in Hz
FIL min
Lower inner grid frequency value in Hz
FOL max
Upper outer grid frequency limit value in Hz
Содержание IG-TL 3.0
Страница 2: ...0...
Страница 4: ...2...
Страница 14: ...12...
Страница 15: ...General Information...
Страница 16: ......
Страница 23: ...Installation and Startup...
Страница 24: ......
Страница 58: ...56...
Страница 59: ...Operation...
Страница 60: ......
Страница 97: ...Troubleshooting and Maintenance...
Страница 98: ......
Страница 119: ...117 Tightening torque 2 Nm 2 1 5 1 1 1 1 1 1 2 6 1 3 2 ON 7...
Страница 124: ...122...
Страница 125: ...Appendix...
Страница 126: ......
Страница 137: ...135...
Страница 138: ...136...
Страница 139: ...137...