DC-Side Termi-
nals
Connecting alu-
minum cables
(DC)
The DC-side terminals are designed for connecting single-wire, round aluminum cables.
The following points must be taken into account when connecting aluminum cables due to
the non-conducting oxide layer of aluminum:
-
The reduced rated currents for aluminum cables
-
The connection requirements listed below
Reduced rated currents for aluminum cables:
Connection requirements:
Carefully clean off the oxide layer of the stripped cable end, e.g., using a knife.
After removing the oxide layer of the cable end, rub in a neutral grease, e.g., acid- and
alkali-free Vaseline.
Then immediately connect to the terminal.
Repeat the steps above whenever the cable is disconnected and then reconnected.
Polarity Reversal
of Solar Module
Strings
The inverter comes standard with 6 metal slugs in fuse holders in the connection area. The
inverter is designed so that a reverse polarity of all solar module strings will not cause any
damage to the inverter when these metal slugs are used.
DC+
DC-
Rated cross section
Reduced rated current
2.5 mm²
20 A
4 mm²
27 A
6 mm²
35 A
10 mm²
48 A
16 mm²
64 A
NOTE!
Take into account local specifications when configuring cable cross sec-
tions.
IMPORTANT!
Do not use brushes, files or sandpaper. Aluminum particles may get stuck
and can transfer to other cables.
1
2
3
Содержание IG Plus 100 V-1
Страница 2: ...0...
Страница 4: ...2...
Страница 10: ...8...
Страница 16: ...14...
Страница 17: ...General Information...
Страница 18: ......
Страница 20: ...18 Safety symbols Risk of serious injury and damage due to incorrect operation...
Страница 24: ...22...
Страница 25: ...Installation and Startup...
Страница 26: ......
Страница 31: ...29 g 16 Strain relief for solar module strings 17 6 DC terminals 18 DC main switch Item Description...
Страница 76: ...74 1 2 6 x 18...
Страница 80: ...78 Closing Fronius IG Plus Closing Fronius IG Plus 1 1 3 2 1 1 2 3 2 4 1 3...
Страница 89: ...Operation...
Страница 90: ......
Страница 106: ...104 Options If the DatCom component for the required options is not available the message N A not available is shown...
Страница 126: ...124...
Страница 127: ...Troubleshooting and Maintenance...
Страница 128: ......
Страница 146: ...144 Disconnect DC wire Disconnect AC wire 8 9...
Страница 150: ...148...
Страница 151: ...Appendix...
Страница 152: ......
Страница 164: ...162...
Страница 165: ...163 g...
Страница 167: ...165 g...