48
412
Fixed voltage mode has been selected
instead of MPP voltage mode, and the
fixed voltage has been set to too low or
too high a value.
-
**)
415
Safety cut-out via option card or RECER
-
BO has triggered
The inverter is not feeding
any energy into the grid.
*)
416
No communication possible between
power stage set and control system.
The inverter will automati
-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid
*)
417
Hardware ID problem
The inverter will automati
-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid
Update inverter firm
-
ware; *)
419
Unique ID conflict
420
No communication possible with the Fro
-
nius Datamanager
421
HID range error
425
Unable to communicate with the power
stage set
426 -
428
Possible hardware fault
431
Software problem
The inverter is not feeding
any energy into the grid.
Perform AC reset
(switch automatic circuit
breaker off and on
again); update inverter
firmware; *)
436
Functional incompatibility (one or more
PC boards in the inverter are not com
-
patible with each other, e.g. after a PC
board has been replaced)
The inverter will automati
-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid
Update inverter firm
-
ware; *)
437
Power stage set problem
438
Functional incompatibility (one or more
PC boards in the inverter are not com
-
patible with each other, e.g. after a PC
board has been replaced)
The inverter will automati
-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid
Update inverter firm
-
ware; *)
443
Intermediate circuit voltage too low or
asymmetric
The inverter is not feeding
any energy into the grid.
*)
445
-
Compatibility error (e.g. due to re
-
placement of a PC board)
-
Invalid power stage set configura
-
tion
The inverter is not feeding
any energy into the grid.
Update inverter firm
-
ware; *)
447
Insulation fault
The inverter is not feeding
any energy into the grid.
*)
448
Neutral conductor not connected
450
Guard cannot be found
Code
Description
Behaviour
Remedy