Options
OPT/i CU flow
temperature
sensor
This option is available for the following devices:
-
CU 800i
-
CU 800i /460 V
-
CU 800i Pro
The OPT/i CU flow temperature sensor option offers monitoring of the coolant temperat-
ure and flow rate.
Coolant temperature monitoring and flow monitoring are parts of an installation set and
cannot be ordered separately.
The CU 1100i, CU 1100i /460V, CU 1100i /MV, CU 1100i / MV RVP, CU 1200i Pro /MC
and CU 1400i Pro /MC cooling units have this option installed as standard.
Coolant temperature monitoring
A temperature sensor monitors the coolant return temperature during welding.
How it works:
-
If the temperature of the coolant reaches 68 °C (154.4 °F)
-
The power source outputs a warning
-
The welding current is not interrupted
-
The cooling unit remains operational
-
If the temperature of the coolant exceeds 70 °C (158 °F)
-
The power source outputs an error message
-
The temperature sensor interrupts the welding current
-
The cooling unit remains operational
-
The temperature sensor restores the welding current when the coolant temperat-
ure falls to 65 °C (149 °F)
Flow monitoring
A flow sensor monitors the coolant flow during welding.
How it works:
-
If the coolant flow falls to between 1 and 0.7 l/min (0.26 - 0.18 gal./min [US])
-
The power source outputs a warning
-
The welding current is not interrupted
-
The cooling unit remains operational
-
If the coolant flow drops below 0.7 l/min (0.18 gal./min [US])
-
The power source outputs an error message
-
Flow monitoring interrupts the welding current
-
The cooling unit remains operational
-
If the coolant flow drops below 0.4 l/min (0.11 gal./min [US])
-
The power source outputs an error message
-
Flow monitoring interrupts the welding current
-
The cooling unit is switched off
22
Содержание CU 1100i
Страница 2: ......
Страница 16: ...16...
Страница 17: ...General information 17...
Страница 18: ...18...
Страница 26: ...26...
Страница 27: ...Connections and mechanical com ponents 27...
Страница 28: ...28...
Страница 31: ...Installation and commissioning 31...
Страница 32: ...32...
Страница 45: ...Close the cover on the cooling unit connection 3 45 EN...
Страница 46: ...46...
Страница 47: ...Troubleshooting 47...
Страница 48: ...48...
Страница 53: ...Care maintenance and disposal 53...
Страница 54: ...54...
Страница 70: ...70...
Страница 71: ...Technical data 71...
Страница 72: ...72...
Страница 82: ...82...
Страница 83: ...83 EN...