Troubleshooting
Froling GmbH, Industriestraße 12, 4710 Grieskirchen, AUSTRIA
Page 49
www.froling.com
B0600008_US
6
Error number /
Error message
Error information text /
Cause of Error
Troubleshooting
3
Secondary air
damper blocked
Deviation of more than 5% be-
tween position and control signal
for more than 5 minutes
Actuator not turning
Actuator incorrectly fitted
Incorrect direction of rotation
Movement of damper impeded
Connection cable defective
Check actuator and mechanics
Ask a licensed electrician to check
actuator cable and connections
Correct assembly: the damper
must be closed at secondary air
signal 0%
Ask a licensed electrician to swap
connections for "open" and "close"
at plug within Boiler Control Sys-
tem
Check to see if damper is jammed
Ask a licensed electrician to check
actuator cable and connections
4
Boiler has air leak
Safety time limit for checking for
wrong air expired:
If the secondary air signal is 0%
and the flue gas temperature is
above 100°C this time starts to
run. If it is certain that within this
time the two values do not change,
the error note “Boiler has air leak”
will be displayed
Wood in combustion chamber may
have “bridged” during combustion
Check gaskets at all boiler doors
and covers for air leakage,
Check correct assembly of lambda
probe
Ask your boiler dealer for mainte-
nance
25
EMERGENCY OFF
switch was activat-
ed
Emergency Off Switch was activat-
ed
In case no Emergency Off Switch is
installed connection plugs shall be
looped
Follow emergency procedure “In
the event of runaway fire”
If emergency conditions are cleared
turn on EMERGENCY OFF switch
again
Ask a licensed electrician to loop
connection plugs for Emergency
Off Switch within Boiler Control
System
58
Bus module faulty
before power
switched off
A module connected to the bus sys-
tem dropped out or was discon-
nected
Interruption at bus cable hardware
- no data transfer or control power
supply
Electronic component malfunction
at connected module
Reconnect module to the bus sys-
tem
Ask a licensed electrician to check
bus cable, plug and connections
Ask your boiler dealer to check and
replace connected module
59
ID fan does not
rotate, in spite of
full activation
Safety time limit for checking speed
of induced draft fan expired
No confirmation (approx. 2min)
from ID fan speed sensor
Ask a licensed electrician to check
plug connection and connection ca-
ble of the ID fan, as well as the po-
sition of the speed sensor
Ask your boiler dealer to check and
replace induced draft fan
63
001 EEPROM Read
error
Read or write function of the
EEPROM memory does not work
Ask your boiler dealer to check
boiler control core module
64
002 EEPROM Zero
checksum
All system and parameter settings
are reset to manufacturer's stand-
ard settings
Set system configuration and Own-
er’s parameters again!
Error automatically cancelled after
acknowledge