Boiler Maintenance
Page 44
B0600008_US
v
5
Cleaning the flue channels both sides of the Combustion Chamber
Open the Insulation Door and Combus-
tion Chamber Door
Check the passage to the left and right
of the Combustion Chamber for ash
deposits
The amount of ash will depend on the
type of fuel used!
Clean the passages with a small brush
and remove any fallen ash
5.2.3
Monthly Maintenance
Cleaning the grate
Open the Insulation Door and Fuel
Loading Chamber Door
Remove the grate (B)
Remove the ash deposits under the
grate to ensure trouble-free flow of
secondary air!
Important! After cleaning under the
grates, add
½
”-1” of ash on top of
refractory and cast iron surfaces to
protect them.
5.2.4
Annual Maintenance
Cleaning flue gas pipe and flue gas sensor
Mark existing mounting position carefully
Release the retaining screw and remove the sensing element from
the Flue Gas Connector
Clean the Flue Gas Pipe between the Boiler and the Chimney with a
chimney sweep brush
Wipe off the sensing element with a clean cloth
Slide in the flue gas sensing element to the marked position and
secure it gently with the retaining screw
Clean behind the steel aprons. Focus attention on the primary air
inlets.
B