Assembly | 6
M2250322_en | Installation instructions Wood chip boiler T4e 200-350
49
6.5.3 Mains connection
T4e 200-250:
At the back of the boiler:
r
Release the locking mechanism and pull the mains plug down and out
r
Open the plug and connect the mains connection cable
Ä
Flexible sheathed cable must be used for the wiring; this must be of the correct
size to comply with applicable regional standards and regulations.
Ä
The power supply line (mains connection) must be fitted with a C16 A fuse by the
customer.
T4e 300-350:
r
Remove the cover plate along with the main switch from the back of the boiler
r
Run the mains connection cable through the cable gland in the cover plate and
connect it to the terminal blocks
Ä
Flexible sheathed cable must be used for the wiring; this must be of the correct
size to comply with applicable regional standards and regulations.
Ä
The power supply line (mains connection) must be fitted with a C25A fuse by the
customer.