FRIULINOX ALI GROUP S.R.L. A SOCIO UNICO
30
Translation of the original instructions
Via Treviso 4, 33083 Taiedo di Chions (PN) - Italy
Service
M
an
u
al
Label
Machine configuration
Default
min
MAX
Conf61
Dripping time
1 min
0 min
90 min
Conf62
Compressor with hot gas defrosting activation delay
0 sec
0 sec
600 sec
Conf63
Temperature below which the defrosting can start
3°C
-10°C
30°C
Conf64
Delta fan stop Temperature after a defrost
5°C
0°C
10°C
Conf65
Comp. Time ON in Positive cycles with faulty Chamber Probe
3 min
0 min
60 min
Conf66
Comp. Time OFF in Positive cycles with faulty Chamber Probe
7 min
0 min
60 min
Conf67
Comp. Time ON in Negative cycles with faulty Chamber Probe
8 min
0 min
60 min
Conf68
Comp. Time OFF in Negative cycles with faulty Chamber Probe
2 min
0 min
60 min
Conf69
Compressor switch-on from Power-On delay
2 min
0 min
30 min
Conf70
Minimum speed settable by the user
1
0
5
Conf71
Maximum speed settable by the user
5
0
5
Conf72
PWM fans starting speed
80%
0%
100%
Conf73
PWM fans starting time
5 sec
0 sec
600 sec
Conf74
Initial splash
1
0
10
Conf75
Machine type: 0=Gastronomy; 1=Pastry
0
0
1
Conf76
PWM fans linearised minimum speed
10% (15%)
0%
100%
Conf77
PWM fans linearised maximum speed
60% (30%)
0%
100%
Conf78
Set Evaporator Fans adjustment enable Temperature
25°C
-50°C
50°C
Conf79
Reserved
0
Conf80
condenser temperature above which the overheated condenser alarm is
activated
80°C
0°C
200°C
Conf81
condenser temperature above which the locked compressor alarm is
activated
90°C
0°C
200°C
Conf82
locked compressor alarm delay
1 min
0 min
15 min
Conf83
Compressor switch-off delay (Pumpdown)
10 sec
0 sec
600 sec
Conf84
Solenoid switch-on delay (Pumpdown)
60 sec
0 sec
600 sec
Conf85
Reserved
0
Conf86
fans operation in defrosting:
0=parallel to compressor/heaters; 1=always ON
1
0
1
Conf87
Evaporator probe enable: 0=no; 1=yes
1
0
1
Conf88
Condenser probe enable: 0=no; 1=yes
0
0
1
Conf89
Duration of a power failure during a cycle above which a cycle is
interrupted
15min
0min
60min
Conf90
Instrument behaviour when power is restored
0 = the cycle will be interrupted; 1 = the cycle will be restarted
2 = the cycle will be restarted if the interruption lasted less than parameter
Conf89
1
0
2
Conf91
Reserved
1
Conf92
evaporator fan speed during dehumidification
2
0
5
Conf93
evaporator fan switch-off delay from compressor / heating element switch-
off (only valid for operation in parallel)
0sec
0sec
240sec
Conf94
Cycle time for switch-on of the evaporator fans (valid when the fans have
to be switched off)
60sec
0sec
600sec
Conf95
Evaporator fan switch-on time within the cycle time Conf94
60sec
0sec
600sec
Conf96
Evaporator Ventilation: 0=PWM; 1-4=NumInverter
0
0
4
Conf97
evaporator fan delay from door closure
3sec
0sec
240sec
Conf98
Inverter fans speed 1
10.0 Hz
0.0 Hz
100.0 Hz
Conf99
Inverter fans speed 2
20.0 Hz
0.0 Hz
100.0 Hz
Conf100 Inverter fans speed 3
30.0 Hz
0.0 Hz
100.0 Hz
Conf101 Inverter fans speed 4
40.0 Hz
0.0 Hz
100.0 Hz
Conf102 Inverter fans speed 5
50.0 Hz
0.0 Hz
100.0 Hz
Conf103 PWM fans speed 1
20%
0%
100%