COMPONENT TESTING
Reversing Valve Description And Operation
The Reversing Valve controls the direction of refrigerant flow to the indoor and outdoor coils. It consists of a
pressure-operated, main valve and a pilot valve actuated by a solenoid plunger. The solenoid is energized during
the heating cycle only. The reversing valves used in the RAC system is a 2-position, 4-way valve.
The single tube on one side of the main valve body is the high-pressure inlet to the valve from the compressor. The
center tube on the opposite side is connected to the low pressure (suction) side of the system. The other two are
connected to the indoor and outdoor coils. Small capillary tubes connect each end of the main valve cylinder to the
“A” and “B” ports of the pilot valve. A third capillary is a common return line from these ports to the suction tube
on the main valve body. Four-way reversing valves also have a capillary tube from the compressor discharge tube
to the pilot valve.
The piston assembly in the main valve can only be shifted by the pressure differential between the high and low
sides of the system. The pilot section of the valve opens and closes ports for the small capillary tubes to the main
valve to cause it to shift.
NOTE: System operating pressures must be near normal before valve can shift.
A
B
Figure 601 (Reserving Valve)
Содержание VRP12K
Страница 30: ...30 OPERATION FreshAire Control To engage the FreshAire system flip the switch into the ON position ...
Страница 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Страница 47: ...47 OPERATION Component Identification Indoor Blower BLDC Counter Clockwise Impeller 600 1300 RPM ...
Страница 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Страница 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Страница 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Страница 177: ...177 UPDATING VRP FIRMWARE Or ...
Страница 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Страница 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Страница 194: ...194 UPDATING VRP FIRMWARE Retrieving VRP Data Right Click Data txt Send to Compressed zipped folder ...
Страница 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Страница 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Страница 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Страница 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Страница 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...
Страница 214: ...214 PARTS CATALOG 36k Control Box Diagram Figure 906 12 12 11 13 10 8 4 3 2 16 5 6 7 1 9 10 9 10 11 11 14 15 ...