Determining the Indoor CFM
Model
VRP12K/ VRP12R
VRP24K/ VRP24R
VRP36K
Air Flow Data
Indoor CFM
Low
High
Low
High
Low
High
.10” ESP*
488
559
472
850
-
-
.15 ESP*
-
-
-
-
1015
1200
.20” ESP
393
466
432
778
875
1160
.30” ESP
292
383
391
703
750
1080
.40” ESP
200
304
348
626
565
970
.50” ESP
104
234
308
555
440
835
* Rated at 0.10” ESP, High and includes 0.08” ESP for factory installed 1” filter
Correct CFM (if needed): Correction Multipliers
230V
1.00
208V
0.97
265V
Heating
1.00
Cooling
0.95
Explanation of charts
Chart A is the nominal dry coil VRP CFMs. Chart B is the correction factors beyond nominal conditions.
1 ½ TON SYSTEM ( 18,000 Btu)
Operating on high speed @ 230 volts with dry coil
measured external static pressure .10
Air Flow = 450 CFM
In the same SYSTEM used in the previous example but having a WET coil you must use a correction factor of .95 (i.e. 450 x .95=428
CFM) to allow for the resistance (internal) of the condensate on the coil.
It is important to use the proper procedure to check external Static Pressure and determine actual airfl ow. Since in the case of the VRP,
the condensate will cause a reduction in measured External Static Pressure for the given airfl ow.
It is also important to remember that when dealing with VRP units that the measured External Static Pressure increases as the
resistance is added externally to the cabinet. Example: duct work, filters, grilles.
Indoor Airflow Data
The VRP A series units must be installed with a free return air configuration. The table below lists the indoor airflow at corresponding
static pressures. All units are rated at low speed.
The VRP units are designed for either single speed or two fan speed operation. For single speed operation refer to the airflow table
below and select the most appropriate CFM based on the ESP level. Connect the fan output from the thermostat to the unit on either the
GL terminal for low speed or to the GH terminal for high speed operation.
For thermostats with two‑speed fan outputs connect the low speed output to the unit GL terminal and the high speed output to the GH
terminal.
EXTERNAL STATIC PRESSURE
Содержание VRP12K
Страница 30: ...30 OPERATION FreshAire Control To engage the FreshAire system flip the switch into the ON position ...
Страница 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Страница 47: ...47 OPERATION Component Identification Indoor Blower BLDC Counter Clockwise Impeller 600 1300 RPM ...
Страница 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Страница 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Страница 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Страница 177: ...177 UPDATING VRP FIRMWARE Or ...
Страница 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Страница 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Страница 194: ...194 UPDATING VRP FIRMWARE Retrieving VRP Data Right Click Data txt Send to Compressed zipped folder ...
Страница 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Страница 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Страница 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Страница 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Страница 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...
Страница 214: ...214 PARTS CATALOG 36k Control Box Diagram Figure 906 12 12 11 13 10 8 4 3 2 16 5 6 7 1 9 10 9 10 11 11 14 15 ...