6

THERMOSTAT

A cross ambient thermostat is used to maintain the desired 

comfort level. The thermostat reacts only to a change in 
temperature at the bulb location. Important to the successful 
operation of the unit is the position of the sensing bulb in relation 
to the evaporator (see Figure 8).

TEST

Remove the wires from the thermostat. Turn the thermostat to 
its coldest position. Check to see if there is continuity between 
the two terminals. Turn the thermostat to its warmest position. 
Check continuity to see if the thermostat contacts open.

Note: 

The temperature must be within the range listed to check 

the thermostat. Refer to the troubleshooting section in this 
manual for additional information on thermostat testing.

LOW AMBIENT BYPASS VALVE (Figure 9)

The HazardGard unit is designed to operate at low outside 

ambient temperatures. This is accomplished by the use of a 
bypass valve installed in the refrigeration circuit. The valve 
is connected between the discharge line at the compressor 
and the suction process tube. The valve responds to suction 
pressure which, when reduced in the system, causes the 
valve to open and bypass hot gas from the high pressure side 
to the low pressure side of the system. The hot gas entering 
the compressor mixes with the cool gas returned through the 
suction line, thus increasing the suction pressure. The valve 
is preset to open when the suction pressure reaches 50 psig. 

This pressure setting cannot be altered. The system can be 

operated at outdoor temperatures as low as 45°

 

F before the 

evaporator coil will begin to accumulate frost.

To determine if the valve operates, block the return air to the 

evaporator coil. Turn on the unit and touch the tube at the 
bypass valve outlet which connects to the suction process 
tube. When the low side pressure reaches approximately 50 
psig, the valve will begin to open and the tube will get hot. This 
method will determine if the valve is responding to the suction 
pressure change.

FIGURE 9 
LOW AMBIENT 
Bypass VALVE

SEALED REFRIGERATION SYSTEM 
REPAIRS

Equipment Required:

1. Voltmeter

2. Ammeter

3. Ohmmeter

4.  E.P.A Approved Refrigerant Recovery System

5.  Vacuum Pump (capable of 200 microns or less vacuum).

6. Acetylene 

Welder

7. 

Electronic Halogen Leak Detector (G.E. Type  

 

H-6 or equivalent).

8.  Accurate refrigerant charge measuring device  

 

such as:

 

a.  Balance Scales - 1/2 oz. accuracy

 

b.  Charging Board - 1/2 oz. accuracy

9.  High Pressure Gauge - (0-400 lbs.)

10.  Low Pressure Gauge - (30" - 150 lbs.)

11.  Vacuum Gauge - (0-1000 microns)

Equipment Must Be Capable of:

1. 

Recovering CFC’s as low as 5%.

2.  Evacuation from both the high side and low side of the 

system simultaneously.

3. 

Introducing  refrigerant  charge  into  the  high  side  of  the 

system.

4. 

Accurately weighing the refrigerant charge actually intro-

duced into the system.

5. Facilities 

for 

fl owing nitrogen through the refrigeration 

tubing during all brazing processes.

RANGE:

 

Thermostat

(Part No. 618-225-02)

60

°

 F ( ± 2

°

 ) to 90

°

 F( ± 4

°

 )

FIGURE 8 
SENSING 
BULB LOCATION

Содержание HAZARDGARD SH15L30-B

Страница 1: ...SH15L30 B SH20L30 B HG SVC PRTS 07 3 07 Room Air Conditioners 60 Hz Models 2007 Service Parts Manual...

Страница 2: ...ntrol Switch 5 Run Capacitor 5 Thermostat 5 Low Ambient Bypass Valve 6 Sealed Refrigeration System Repairs 6 Hermetic Component Replacement 7 Special Procedure in the case of Compressor Motor Burn Out...

Страница 3: ...TING FOR CLASS I DIVISION 2 GROUPS A B C D Model Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth...

Страница 4: ...hell of the compressor continuity grounded motor replace compressor 5 Should continuity exist between terminals R and S but not between terminals C and S and C and R the internal overload may be open...

Страница 5: ...can be used for each motor or a dual rated capacitor can be used for both The capacitor s primary function is to reduce the line current while greatly improving the torque characteristics of a motor...

Страница 6: ...ressure reaches 50 psig This pressure setting cannot be altered The system can be operated at outdoor temperatures as low as 45 F before the evaporator coil will begin to accumulate frost To determine...

Страница 7: ...pump to the high side and low side of the system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate the system to an absolute holding pressure of 200 microns or less 12 Resta...

Страница 8: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Страница 9: ...SOR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for nam...

Страница 10: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Страница 11: ...11 WIRING DIAGRAM MODELS SH15L30 B and SH20L30 B...

Страница 12: ...12 HAZARDGARD CABINET PARTS...

Страница 13: ...13 HAZARDGARD CHASSIS PARTS...

Страница 14: ...1 399 RELAY SOLID STATE 61108800 2 2 399 6 THERMOSTAT 61822502 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 150 HARNESS WIRE COMP 61821308 1 1 399 REFRIGERATION...

Страница 15: ...4905 1 743 30 SCROLL 61817505 1 743 32 BASE PAN 61803444 1 1 730 34 BOLT COMP MOUNT 91400400 3 3 791 35 PLENUM ASSEMBLY 61831006 1 1 753 36 OUTER SHELL 61825708 1 770 36 OUTER SHELL 61825709 1 770 37...

Страница 16: ...rranty period providing the unit is returned to an authorized Friedrich Repair Station located within the Continental United States The Friedrich warranty does not cover 1 Any charges for removal tran...

Отзывы: