background image

5

FAN MOTOR 

(Figure 4)

A 230 volt single phase permanent split capacitor motor is 

used to drive the evaporator blower and condenser fan. A 
running capacitor is wired across the start and run terminals 
of the motor.

The motor is totally enclosed and is protected with a line volt-

age overload located internally of the motor. The motor shaft 
is stainless steel to resist corrosion.

FAN MOTOR – TEST

Disconnect power to the unit.

 

1.  Determine that the capacitor is serviceable.

 

2.  Disconnect the black lead from the circuit board.

 

3.  Apply "live" test cord leads to the common terminal of 

the capacitor and the black lead. The motor should run 
at high speed.

SOLID STATE RELAY 

(Figure 5)

Two 50 amp rated 208/230 volt solid state relays are used to 

energize the compressor and fan motor. Terminals 3 and 4 are the 
208/230 volt line side. Terminals 1 and 2 are load side contacts.

FIGURE 4 
FAN MOTOR

SYSTEM CONTROL SWITCH 

(Figure 6)

This switch is double pole, single throw. Check for continuity 

between terminals 2 and 3, and 5 and 6.

FIGURE 6 
SWITCH, ON-OFF

CAPACITOR, RUN

A run capacitor is wired across the auxiliary and main winding 

of a single phase permanent split capacitor motor such as the 
compressor and fan motors. A single capacitor can be used for 
each motor or a dual rated capacitor can be used for both.

The capacitor’s primary function is to reduce the line current 

while greatly improving the torque characteristics of a motor. 

The capacitor also reduces the line current to the motor by 

improving the power factor of the load. The line side of the 
capacitor is marked with a red dot and is wired to the line side 
of the circuit (see Figure 7.)

RED DOT

RUN CAPACITOR

FAN
MOTOR

COMPRESSOR

FIGURE 7  RUN CAPACITOR HOOK–UP

CAPACITOR – TEST

1.  Remove the capacitor from the unit.

2.  Check for visual damage such as bulges, cracks, or 

leaks.

3.  For dual rated capacitors, apply an ohmmeter lead to 

the common (C) terminal and the other probe to the 
compressor (HERM) terminal. A satisfactory capacitor will 
cause a defl ection on the pointer, then gradually move back 
to infi nity.

4.  Reverse the leads of the probe and momentarily touch the 

capacitor terminals. The defl ection of the pointer should be 
two times that of the fi rst check if the capacitor is good.

5.  Repeat steps 3 and 4 to check the fan motor capacitor.

NOTE:

 A shorted capacitor will indicate a low 

resistance and the pointer will move more to the “0” 
end of the scale and remain there as long as the 
probes are connected. An open capacitor will show 
no movement of the pointer when placed across the 
terminals of the capacitor. 

LED indicates 

contacts closed 

when lit

Line side

Load side

FIGURE 5 
SOLID STATE 
RELAY

Содержание HAZARDGARD SH15L30-B

Страница 1: ...SH15L30 B SH20L30 B HG SVC PRTS 07 3 07 Room Air Conditioners 60 Hz Models 2007 Service Parts Manual...

Страница 2: ...ntrol Switch 5 Run Capacitor 5 Thermostat 5 Low Ambient Bypass Valve 6 Sealed Refrigeration System Repairs 6 Hermetic Component Replacement 7 Special Procedure in the case of Compressor Motor Burn Out...

Страница 3: ...TING FOR CLASS I DIVISION 2 GROUPS A B C D Model Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth...

Страница 4: ...hell of the compressor continuity grounded motor replace compressor 5 Should continuity exist between terminals R and S but not between terminals C and S and C and R the internal overload may be open...

Страница 5: ...can be used for each motor or a dual rated capacitor can be used for both The capacitor s primary function is to reduce the line current while greatly improving the torque characteristics of a motor...

Страница 6: ...ressure reaches 50 psig This pressure setting cannot be altered The system can be operated at outdoor temperatures as low as 45 F before the evaporator coil will begin to accumulate frost To determine...

Страница 7: ...pump to the high side and low side of the system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate the system to an absolute holding pressure of 200 microns or less 12 Resta...

Страница 8: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Страница 9: ...SOR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for nam...

Страница 10: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Страница 11: ...11 WIRING DIAGRAM MODELS SH15L30 B and SH20L30 B...

Страница 12: ...12 HAZARDGARD CABINET PARTS...

Страница 13: ...13 HAZARDGARD CHASSIS PARTS...

Страница 14: ...1 399 RELAY SOLID STATE 61108800 2 2 399 6 THERMOSTAT 61822502 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 150 HARNESS WIRE COMP 61821308 1 1 399 REFRIGERATION...

Страница 15: ...4905 1 743 30 SCROLL 61817505 1 743 32 BASE PAN 61803444 1 1 730 34 BOLT COMP MOUNT 91400400 3 3 791 35 PLENUM ASSEMBLY 61831006 1 1 753 36 OUTER SHELL 61825708 1 770 36 OUTER SHELL 61825709 1 770 37...

Страница 16: ...rranty period providing the unit is returned to an authorized Friedrich Repair Station located within the Continental United States The Friedrich warranty does not cover 1 Any charges for removal tran...

Отзывы: