Owner’s & Installation Manual
11
ENGLISH
Installation instruction
If entering into ESP setup mode by using
button, it indicates as the picture
below.
2
Select ESP fan step by pressing
button. (01: very low, 02: low,
03: medium, 04: high, 05: very high)
3
Move to ESP value setting by pressing
button.
(It is 000 when delivering
from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP
value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)
5
Function code,
ESP code
ESP value
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
1
Function Code
ESP value
ESP step
Installer Setting - E.S.P.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
• When setting ESP value on the product without very weak wind or power wind function, it
may not work.