15
8.
To select the required sensitivity, set DIP switch 5 of
SW3 as follows:
ON = HIGH sensitivity
OFF =
LOW sensitivity
Note:
The recommended setting is HIGH. However,
in cases of extreme environmental problems or if
unexplained false alarms are experienced, it may be
necessary to set the sensitivity to LOW. Setting the
device to LOW sensitivity will require a greater amount
of movement in order to trigger the device.
9.
Connect the PP3 Alkaline battery to the battery
clip. The LED behind the lens will rapidly flash for
approximately 2-3 minutes until the PIR has stabilised.
The LED will then stop flashing and turn OFF.
10.
Check that the detector Circuit Board is located and
set in the correct position to give the detection zone
pattern required.
To adjust the PCB position simply slide it up or down
ensuring that the location legs are aligned with the
required position number marked on the board.
11.
To refit the PIR detector to the rear cover, offer the
detector up to the rear cover and locate the clips in the
top edge into the rear cover. Push the lower edge of
the detector into place and refit the fixing screw in the
bottom edge of the PIR to secure in position. Do not
over-tighten the fixing screws as this may damage the
casing.
Testing the PIR Detector:
12.
Ensure that the LED indicator has stopped flashing
rapidly.
13.
Use the and buttons to scroll through
the menu until ‘
WALK TEST
’ is displayed and press
.
‘
Walk Test Waiting…
’ will be displayed.
14.
Walk into and move slowly around the protected
area, each time the detector senses movement the
LED indicator behind the lens will flash.
In addition, the Control Panel will beep to indicate that
the alarm signal has been received and the identity
of the zone that the detector is configured for will be
displayed.
15.
If necessary remove the detector from the wall and
adjust the mounting position of the circuit board within
the detector. Repeat step 14 until the detection range
is correct for your needs. (In most cases no adjustment
will be required).
16.
Remove the back cover of the PIR detector. The
Control Panel should beep and display “
Accessory
Tamper
” to show that the detector’s tamper switch has
been activated.
17.
Press to return to the top level menu of TEST
MODE.
18.
Reconfigure the PIR Detector for Normal Operation
with DIP switch 4 of SW3 OFF and refit in position on
the wall.
IMPORTANT:
In normal operation, the LED indicator
behind the detector lens will not flash on movement
detection, (unless the battery is low).
Note:
When the detector is fully installed i.e. battery
cover fitted and in operating mode; in order to conserve
power and maximise battery life the PIR Detector will
only detect movement if there has been no movement
detected within the previous 2 minutes.
1
6m
3
9m
5
12m
PCB Position Range
������������
�������������
���������
���������������
���������������
���������
�
�
�
�
�
������������
���������
���������������
��
���
���
���
���
���
���
���
�
��
���
���
���
���
�
��
�
��
�
1
2
3
4
5
ON
1
2
3
4
5
ON