SIRe Competent Air Curtains Water
31
GB
Filter timer on/off
Filter timer setting
Last filter change
> Installer menu > Filter guard
settings
Filter timer on/off
Filter timer setting
Last filter change
Installer menu > Filter guard
settings
Open door step. diff.
Sensor calibration
Control range limit
Installer menu > Heating
settings
Heating settings
Filter guard settings
External control
> Installer menu
Open door step. diff.
Sensor calibration
Control range limit
> Installer menu > Heating
settings
Filter timer on/off
Filter timer setting
Last filter change
> Installer menu > Filter guard
settings
Room temp. sensor
Outdoor temp. sensor
> Installer menu > Heating
settings > Sensor calibration
Room temp. sensor
•
0.0 K
> Installer menu > Heating
settings > Sensor calibration
Control range limit
•
35°C
> Installer menu > Heating
settings
Filter timer setting
•
750 h
> Installer menu > Filter guard
settings
Last filter change
0 h
> Installer menu > Filter guard
settings
Filter guard settings
External control
General settings
> Installer menu
External on/off
0-10V fan control
> Installer menu > External
control
External on/off
0-10V fan control
> Installer menu > External
control
Calibration sensors
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for e2K gives an increase of the
displayed value of 2 degrees).
Factory setting:
Room temperature sensor: 0.0 K (-10 K – 10
K)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35 °C.
Factory setting:
Control range limit temperature: 35 °C (5 –
35 °C)
Filter guard settings
Filter alarm alarms when the set fixed run
time has been exceeded.
Filter timer setting
Under Filter timer setting, set the desired run
time to between 50 and 9950 hours.
Factory setting:
Filter timer setting
750 h (50 - 9950 h)
Filter timer on/off
Filter alarm is activated by selecting On,
under Filter timer on/off.
Factory setting:
Filter timer on/off:
Off (On)
Last filter change
To check the number of run time hours since
the last filter replacement, select Last filter
change.
The time is reset when the filter alarm is
reset. If the time is to be reset before the
alarm has gone, switch the filter timer on and
off.
External control (BMS)
BMS functions can be activated under
External control.
Activate
External on/off
(5-30V AC/DC from
BMS) or
0-10V fan control
by selecting On
under the respective one. See diagram on
next page and
Connecting external control.