14
RAR 200 A/E/W
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
RAR210W
max
1000
–
–
–
–
3,7
28,8
0,04
6,3
min
700
4,0
52,6
0,01
43,9
3,0
30,5
0,04
4,3
RAR215W
max
1600
–
–
–
–
5,8
28,6
0,07
3,2
min
1000
5,8
50,8
0,15
12,8
4,3
30,7
0,05
1,9
RAR220W
max
2000
–
–
–
–
7,3
28,8
0,09
5,7
min
1400
8,1
53,0
0,28
43,5
5,9
30,4
0,07
3,8
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
RAR210W
max
1000
–
–
–
–
2,9
26,7
0,04
4,3
min
700
–
–
–
–
2,4
28,0
0,03
2,9
RAR215W
max
1600
–
–
–
–
4,5
26,4
0,05
2,2
min
1000
–
–
–
–
3,4
28,0
0,04
1,3
RAR220W
max
2000
–
–
–
–
5,8
26,6
0,07
3,9
min
1400
–
–
–
–
4,7
27,9
0,06
2,6
Output charts water RAR200
RAR200 W
Se www.frico.se för ytterligare beräkningar.
*
1
) Rekommenderad utgående lufttemperatur för en god komfort med optimerat effektuttag.
*
2
) Nominell effekt vid given framlednings- och returtemperatur.
- = vid rådande vattentemperaturer och luftflöden kommer utgående lufttemperatur vara lägre än 35 °C.
Содержание RAR200A
Страница 1: ...RAR 200 A E W SE GB FR NO DE ES NL 16 20 25 29 34 39 44 49 IT...
Страница 8: ...8 RAR 200 A E W...
Страница 9: ...9 RAR 200 A E W...
Страница 10: ...10 RAR 200 A E W...
Страница 54: ......
Страница 55: ......
Страница 56: ...Art no E4475 2014 05 06 S HH S Technical Support tel 46 313368600...