background image

Type

Output 

[kW]

Voltage 

[V]

Minimum 

area* 

[mm

2

]

Control

0

230V~

1,5

PA2510CE03

3

230V~ 

1,5

PA2515CE08

8

400V3~ 

2,5

PA2520CE10

10

400V3~ 

2,5

PA2500C

GB

16

Start-up (E) 

When the unit is used for the first time or 
after a long period of disuse, smoke or odour 
may result from dust or dirt that has collected 
on the element. This is completely normal 
and disappears after a short time. 

Connecting the water coil (W) 

The installation must be carried out by an 
authorised installer. 

The water coil has copper tubes with 

aluminium fins and is suitable for connection 
to a closed water heating system. The heating 
coil must not be connected to a mains 
pressure water system or an open water 
system. 

Note that the unit shall be preceded by a 

regulating valve, see Frico valve kit.  
The water coil is connected on the upper 
side of the unit with ø15 mm smooth copper 
pipe with a suitable coupling or soldering. 
The connections to the heating coil must be 
equipped with shut off valves to allow problem 
free removal. Water coil is equipped with a 
drain valve. A vent valve should be connected 
at a high point in the pipe system. 
Air valves are not included. NOTE: Care must 
be taken when connecting the pipes. Use 
a wrench or similar to hold the air curtain 
connections to prevent straining of the 
pipes and subsequent water leakage during 
connection to water supply pipe-work. 

*) Dimensioning of external wiring shall comply 
with applicable regulations and local deviations 
may occur. 

the distribution board it is to be indicated 
that ”the air curtains can be supplied from 
more than one connection”. 

See wiring diagrams. 

Adjustment of the air curtain and air flow 

The direction and speed of the air flow should 
be adjusted considering the load on the 
opening. Pressure forces affect the air stream 
and make it bend inwards into the premises 
(when the premises are heated and the 
outdoor air is cold).

The air stream should therefore be directed 

outwards to withstand the load. Generally 
speaking, the higher the load, the greater the 
angle that is needed.

Basic setting fan speed 

The fan speed when the door is open is set 
using the control. Note that the air flow 
direction and fan speed may need fine 
adjustment depending on the loading of the 
door.

Filter (W) 

The water coil is protected against dirt and 
blockage by an internal air filter which covers 
the coil face. In environments where the filter 
needs cleaning often, it is advisable to use an 
external intake filter (see accessories pages), 
which provides an easier maintenance, since 
the unit does not need to be opened. When 
an external filter is used, the internal filter is 
removed.

Service, repairs and maintenance  

For all service, repair and maintenance first 
carry out the following:  
1. Disconnect the power supply.
2. The front hatch is removed by removing

the screws on the top of the unit and then
detach the bent edge at the bottom. (Fig.3)

3. After the service, repair and maintenance

reattach the front hatch. Place the hatch
at the lower edge with the bent edge and
fasten on top with screws.

Содержание PA2500C Series

Страница 1: ...Instrukcja obs ugi PA2500C 15 GB 21 PL...

Страница 2: ...t mainly of pictures For translation of the English texts used see the respective language pages GB Pocz tkowe strony zawieraj g wnie rysunki T umaczenie wykorzystanych tekst w angielskich znajduje si...

Страница 3: ...5 345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu 15 53 71 40 min 500 min 500 157 157 PA2500C 3 PA2500C Gland Knock out Knock out Knock out Gland...

Страница 4: ...PA2500C 4 Fig 3 Open the unit A B C TX20...

Страница 5: ...30 mm 60 mm min 60 PA2500C 5 Fig 4 Fig 5 Minimum distance...

Страница 6: ...min 500 mm 20 35 75 210 33 8 3x 5 10 162 PA2500C 6 Fig 6 Mounting with wall brackets Mounting with wall brackets A B C PA2510C 2 pcs PA2515C 2 pcs PA2520C 3 pcs D...

Страница 7: ...DN25 VOS15LF DN15 VOS15NF DN15 VOS20 DN20 VOS25 DN25 PA34TR15 PA2510C PA2515C 1 m PA34TR20 PA2520C 1 m PA2P15 PA2510C PA2515C 1 m PA2P20 PA2520C 1 m PA2PF15 PA2510C PA2515C PA2PF20 PA2520C PAMLK PA250...

Страница 8: ...V3 14 4 2050 36 1 Ambient no heat PA2500C A Type Output kW Airflow m3 h Sound level 1 dB A Voltage motor V Amperage motor A Length mm Weight kg PA2510CA 0 900 1300 43 53 230V 0 5 1050 16 PA2515CA 0 12...

Страница 9: ...PA2210CA PA2215CA PA2220CA Right motor Left motor Only 2 m version PA2500C 9 PA2510CA PA2515CA PA2520CA PA2510CA PA2515CA PA2520CA...

Страница 10: ...2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR M Blue Black Brown C Over heat cut out C C1 L2 PE L1 L N L3 400V 3N L2 PE L1 L N L3 230V 2210CE03 2210CE05 PA2210CE03 PA2210CE05 C3 Run...

Страница 11: ...SENSOR IR C2 Over heat cut out C C1 L2 PE L1 L N L3 400V 3N Over heat C cut out PA2215CE08 PA2220CE10 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m vers...

Страница 12: ...10V HEAT ALARM WATER INTERNAL SENSOR IR PA2210CW PA2215CW PA2220CW M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid Black Brow...

Страница 13: ...PAMLK C NC NO Motor alarm pot free contact M Blue Black Brown C Lo Mid Run Left motor Only 2 m version 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTE...

Страница 14: ...temp C Water flow l s Pressure drop kPa PA2510CW max 1300 5 6 30 6 0 07 5 3 min 900 4 4 32 9 0 05 3 6 PA2515CW max 2100 9 4 31 4 0 11 7 3 min 1250 6 7 34 7 0 08 4 0 PA2520CW max 2600 11 6 31 2 0 14 6...

Страница 15: ...o floor for electrically heated units is 1800 mm For other minimum distances see fig 4 Mounting with wall brackets fig 6 1 Mount the brackets on the wall see fig 6A and dimension drawing fig 1 If the...

Страница 16: ...able regulations and local deviations may occur the distribution board it is to be indicated that the air curtains can be supplied from more than one connection See wiring diagrams Adjustment of the a...

Страница 17: ...reverse order Replacing the water coil W 1 Shut off the water supply to the unit 2 Disconnect the connections to the water coil 3 Remove the mounting screws securing the coil in the unit and lift the...

Страница 18: ...nment moisture can enter the element This should not be seen as a fault but is simply rectified by connecting the appliance to the main supply via a socket without a safety cut out so that the moistur...

Страница 19: ...g dip switches Unit with water heating Dip switch 3 is used for PA2DR optional OFF Actuator SD230 remove the quick connector Black Brown Blue External on off Eg time switch External potential free clo...

Страница 20: ...minutes to vent out the heat if the temperature rises above 50 C again during the following 5 minutes overheating alarm is deployed The red LEDs flash and all the buttons are locked 1 Disconnect the e...

Страница 21: ...s 6 1 Przymocuj wsporniki do ciany patrz rys 6A oraz rysunek wymiarowy rys 1 Je li ciana jest nier wna wsporniki nale y odpowiednio dopasowa 2 Zawie urz dzenie na dolnej kraw dzi wspornik w rys 6B C 3...

Страница 22: ...pod czenia Regulacja kurtyny powietrznej i strumienia powietrza Kierunek i pr dko przep ywu powietrza nale y wyregulowa odpowiednio do r nicy temperatur r nicy ci nie i naporu wiatru zabezpieczanego...

Страница 23: ...ennika wodnego W 1 Odetnij dop yw wody do urz dzenia 2 Od cz przy cza wymiennika wodnego 3 Wykr ruby mocuj ce wymiennik w urz dzeniu po czym wyjmij go z obudowy 4 Zamontuj nowy wymiennik powtarzaj c p...

Страница 24: ...w miejscu o wysokiej wilgotno ci powietrza mo e doj do zawilgocenia elementu grzejnego Nie nale y tego traktowa jako usterki poniewa wystarczy pod czy urz dzenie do zasilania przez gniazdko bez wy cz...

Страница 25: ...nym Prze cznik 3 przeznaczony do obs ugi czujnika drzwiowego PA2DR opcjonalny WY Si ownik SD230 usun szybkoz cze Czarny Br zowy Niebieski Zewn w wy np wy czasowy Zewn trzny styk bezpotencja owy wy PA2...

Страница 26: ...ciep o Je li w ci gu kolejnych 5 minut temperatura ponownie przekroczy 50 C uruchomi si alarm przegrzania Czerwone diody LED b d pulsowa i wszystkie przyciski zostan zablokowane 1 Od cz zasilanie za p...

Страница 27: ...urz dzenia Minimalne odleg o ci Monta przy u yciu uchwyt w ciennych Szt Wyposa enie dodatkowe Gland Open the unit Minimum distance Mounting with wall brackets Pcs Accessories T umaczenie pocz tkowych...

Страница 28: ...e Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 208852 201608...

Отзывы: