background image

PA2500C

GB

18

Trouble shooting  

If the fans are not working or do not blow pro-
perly, check the following: 

• The functions and settings of the built-in

control system.

• That the intake grille/filter is not dirty.

If there is no heat, check the following:

• The functions, internal sensor and settings

of the built-in control system. 

For units with electrical heating, also check the 
following:

• Power supply to electric heater coil; check

fuses and circuit-breaker (if any).

• That the overheat protection for the motors

has not been deployed.

For units with water coil, also check the follo-
wing:

• That the water coil is air free.
• That there is enough water flow.
• That incoming water is heated enough.

If the fault cannot be rectified, please contact 
a qualified service technician. 

Residual current circuit breaker (E) 

When the installation is protected by means 
of a residual current circuit breaker, which 
trips when the appliance is connected, 
this may be due to moisture in the heating 
element. When an appliance containing a 
heater element has not been used for a long 
period or stored in a damp environment, 
moisture can enter the element. 

This should not be seen as a fault, but is 

simply rectified by connecting the appliance 
to the main supply via a socket without a 
safety cut-out, so that the moisture can be 
eliminated from the element. The drying 
time can vary from a few hours to a few days. 
As a preventive measure, the unit should 
occasionally be run for a short time when it is 
not being used for extended periods of time. 

Safety  

For all installations of electrically heated
products should a residual current circuit
breaker 300 mA for fire protection be used.

Keep the areas around the air intake
and exhaust grilles free from possible
obstructions!

The unit may have hot surfaces during
operation and when cooling down!

The unit must not be fully or partially
covered with clothing, or similar
materials, as overheating can result in a
fire risk! (E)

This appliance can be used by children
aged from 8 years and above and persons
with reduced physical, sensory or
mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning
use of the appliance in a safe way and
understand the hazards involved. Children
shall not play with the appliance. Cleaning
and user maintenance shall not be made
by children without supervision.

Содержание PA2500C Series

Страница 1: ...Instrukcja obs ugi PA2500C 15 GB 21 PL...

Страница 2: ...t mainly of pictures For translation of the English texts used see the respective language pages GB Pocz tkowe strony zawieraj g wnie rysunki T umaczenie wykorzystanych tekst w angielskich znajduje si...

Страница 3: ...5 345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu 15 53 71 40 min 500 min 500 157 157 PA2500C 3 PA2500C Gland Knock out Knock out Knock out Gland...

Страница 4: ...PA2500C 4 Fig 3 Open the unit A B C TX20...

Страница 5: ...30 mm 60 mm min 60 PA2500C 5 Fig 4 Fig 5 Minimum distance...

Страница 6: ...min 500 mm 20 35 75 210 33 8 3x 5 10 162 PA2500C 6 Fig 6 Mounting with wall brackets Mounting with wall brackets A B C PA2510C 2 pcs PA2515C 2 pcs PA2520C 3 pcs D...

Страница 7: ...DN25 VOS15LF DN15 VOS15NF DN15 VOS20 DN20 VOS25 DN25 PA34TR15 PA2510C PA2515C 1 m PA34TR20 PA2520C 1 m PA2P15 PA2510C PA2515C 1 m PA2P20 PA2520C 1 m PA2PF15 PA2510C PA2515C PA2PF20 PA2520C PAMLK PA250...

Страница 8: ...V3 14 4 2050 36 1 Ambient no heat PA2500C A Type Output kW Airflow m3 h Sound level 1 dB A Voltage motor V Amperage motor A Length mm Weight kg PA2510CA 0 900 1300 43 53 230V 0 5 1050 16 PA2515CA 0 12...

Страница 9: ...PA2210CA PA2215CA PA2220CA Right motor Left motor Only 2 m version PA2500C 9 PA2510CA PA2515CA PA2520CA PA2510CA PA2515CA PA2520CA...

Страница 10: ...2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR M Blue Black Brown C Over heat cut out C C1 L2 PE L1 L N L3 400V 3N L2 PE L1 L N L3 230V 2210CE03 2210CE05 PA2210CE03 PA2210CE05 C3 Run...

Страница 11: ...SENSOR IR C2 Over heat cut out C C1 L2 PE L1 L N L3 400V 3N Over heat C cut out PA2215CE08 PA2220CE10 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m vers...

Страница 12: ...10V HEAT ALARM WATER INTERNAL SENSOR IR PA2210CW PA2215CW PA2220CW M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid Black Brow...

Страница 13: ...PAMLK C NC NO Motor alarm pot free contact M Blue Black Brown C Lo Mid Run Left motor Only 2 m version 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTE...

Страница 14: ...temp C Water flow l s Pressure drop kPa PA2510CW max 1300 5 6 30 6 0 07 5 3 min 900 4 4 32 9 0 05 3 6 PA2515CW max 2100 9 4 31 4 0 11 7 3 min 1250 6 7 34 7 0 08 4 0 PA2520CW max 2600 11 6 31 2 0 14 6...

Страница 15: ...o floor for electrically heated units is 1800 mm For other minimum distances see fig 4 Mounting with wall brackets fig 6 1 Mount the brackets on the wall see fig 6A and dimension drawing fig 1 If the...

Страница 16: ...able regulations and local deviations may occur the distribution board it is to be indicated that the air curtains can be supplied from more than one connection See wiring diagrams Adjustment of the a...

Страница 17: ...reverse order Replacing the water coil W 1 Shut off the water supply to the unit 2 Disconnect the connections to the water coil 3 Remove the mounting screws securing the coil in the unit and lift the...

Страница 18: ...nment moisture can enter the element This should not be seen as a fault but is simply rectified by connecting the appliance to the main supply via a socket without a safety cut out so that the moistur...

Страница 19: ...g dip switches Unit with water heating Dip switch 3 is used for PA2DR optional OFF Actuator SD230 remove the quick connector Black Brown Blue External on off Eg time switch External potential free clo...

Страница 20: ...minutes to vent out the heat if the temperature rises above 50 C again during the following 5 minutes overheating alarm is deployed The red LEDs flash and all the buttons are locked 1 Disconnect the e...

Страница 21: ...s 6 1 Przymocuj wsporniki do ciany patrz rys 6A oraz rysunek wymiarowy rys 1 Je li ciana jest nier wna wsporniki nale y odpowiednio dopasowa 2 Zawie urz dzenie na dolnej kraw dzi wspornik w rys 6B C 3...

Страница 22: ...pod czenia Regulacja kurtyny powietrznej i strumienia powietrza Kierunek i pr dko przep ywu powietrza nale y wyregulowa odpowiednio do r nicy temperatur r nicy ci nie i naporu wiatru zabezpieczanego...

Страница 23: ...ennika wodnego W 1 Odetnij dop yw wody do urz dzenia 2 Od cz przy cza wymiennika wodnego 3 Wykr ruby mocuj ce wymiennik w urz dzeniu po czym wyjmij go z obudowy 4 Zamontuj nowy wymiennik powtarzaj c p...

Страница 24: ...w miejscu o wysokiej wilgotno ci powietrza mo e doj do zawilgocenia elementu grzejnego Nie nale y tego traktowa jako usterki poniewa wystarczy pod czy urz dzenie do zasilania przez gniazdko bez wy cz...

Страница 25: ...nym Prze cznik 3 przeznaczony do obs ugi czujnika drzwiowego PA2DR opcjonalny WY Si ownik SD230 usun szybkoz cze Czarny Br zowy Niebieski Zewn w wy np wy czasowy Zewn trzny styk bezpotencja owy wy PA2...

Страница 26: ...ciep o Je li w ci gu kolejnych 5 minut temperatura ponownie przekroczy 50 C uruchomi si alarm przegrzania Czerwone diody LED b d pulsowa i wszystkie przyciski zostan zablokowane 1 Od cz zasilanie za p...

Страница 27: ...urz dzenia Minimalne odleg o ci Monta przy u yciu uchwyt w ciennych Szt Wyposa enie dodatkowe Gland Open the unit Minimum distance Mounting with wall brackets Pcs Accessories T umaczenie pocz tkowych...

Страница 28: ...e Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 208852 201608...

Отзывы: