PA2500C
8
2
Water heat - PA2500C W
Type
Output*
3
[kW]
Airflow
[m
3
/h]
∆
t
*2,3
[°C]
Water
volume
[l]
Sound
level*
1
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
PA2510CW
4
900/1300 10,5/8,5
0,38
41,5/50
230V~
0,45
1050
17
PA2515CW
6,5
1250/2100 11,5/10
0,81
41/53,5
230V~
0,6
1560
25,5
PA2520CW
8
1800/2600 11/9
0,74
44,5/54
230V~
0,9
2050
34,5
3
Electrical heat - PA2500C E
Type
Output
step
[kW]
Airflow
[m
3
/h]
∆
t
*2
[°C]
Sound
level*
1
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Voltage [V]
Amperage [A]
(heat)
Length
[mm]
Weight
[kg]
PA2510CE03
2/3
900/1450 11/6,5
41/51
230V~
0,5
230V~/13
1050
19
PA2515CE08
4/8
1400/2200 17,5/11
42/51
230V~
0,7
400V3~/11,5
1560
30
PA2520CE10
5/10
1800/2900 17/10,5
43/53
230V~
1,0
400V3~/14,4
2050
36
1
Ambient, no heat - PA2500C A
Type
Output
[kW]
Airflow
[m
3
/h]
Sound
level*
1
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
PA2510CA
0
900/1300
43/53
230V~
0,5
1050
16
PA2515CA
0
1250/2100
44/54
230V~
0,7
1560
23,5
PA2520CA
0
1800/2600
44/55
230V~
1,0
2050
32
*
1
) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At
lowest/highest airflow.
*
2
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
3
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
Protection class for units with electrical heating: IP20.
Protection class for units without heating and units with water heating: IP21.
CE compliant.
Type
C1 Mid
[mF]
C2 Low
[mF]
C2 Run
[mF]
PA2510CA
10
6
4
PA2515CA
14
10
4
PA2520CA
10
6
4
PA2510CE03
10
6
4
PA2515CE08
14
10
4
PA2520CE10
10
6
4
PA2510CW
10
6
4
PA2515CW
14
10
4
PA2520CW
10
6
4