S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 86
COMMUNICATIONS SETUP
APPENDIX B
QUANTUM™ LX PANEL SOFTWARE UPDATE PROCEDURE
Access the Software Maintenance screen by setting the User Level to 2, then clicking on Menu, then Service, and finally
Software Maintenance.
The following selections have been provided:
1)
Save Setpoints - Use this option to save all
setpoints and custom text to a local computer as
a form of backup.
•
Ensure that all setpoint values have been
documented as a safety precaution.
•
Click on the [Save Setpoints] button.
•
The wording on the [Save Setpoints] button
will be replaced with Please Wait…
•
When finished, the [Save Setpoints] button
will return to normal.
•
A new window will pop up with a link to
download the recently saved setpoints. Right
–click on the link, and select “Save As”. The
browser will then allow the user to select a
directory location. NOTE: Do not change the
name of the file or else future setpoint
restoration operations may fail.
•
Press numeral [Exit] to exit and reboot back
to the Level 0 Operating Status screen.
2) Full System Install - Use this option to install the
entire operating system. This function will not
overwrite any setpoints or custom text that may have
previously been setup.
•
Ensure that all setpoint values have been
documented as a safety precaution.
•
Click on the [Full System Install] button.
•
A new window will appear requesting the
user to select a file to upload. The “Browse”
button permits the user to locate the file by
navigating through the system’s directory
structure. Once the System Install File has
been located, click “Upload File” to allow the
process to continue.
•
The wording on the [Full System Install]
button will be replaced with Please Wait…
•
When finished, the [Full System Install]
button will return to normal.
•
Press numeral [Exit] to exit and reboot back
to the Level 0 Operating Status screen.
3)
Restore Setpoints - Use this option to restore all
setpoints and custom text from a local computer
to the Quantum™. This would be useful in the
event that the original setpoints would need to be
reloaded.
•
Ensure that all setpoint values have been
documented as a safety precaution.
•
Click on the [Restore Setpoints] button.
•
A new window will appear requesting the
user to select a file to upload. The “Browse”
button permits the user to locate the file by
navigating through the system’s directory
structure. Once the Setpoints Backup File
has been located, click “Upload File” to allow
the process to continue.
•
The wording on the [Restore Setpoints]
button will be replaced with Please Wait…
•
When finished, the [Restore Setpoints]
button will return to normal.
•
Press numeral [Exit] to exit and reboot back
to the Level 0 Operating Status screen.
4) Exit - Use this selection to leave this screen, the
panel will reboot and return to the Operating Status
screen.