FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL S90-510 CS (MAR 07)
COMMUNICATIONS SETUP Page 19
RETURN Warnings & Shutdowns - Page 3 data:
$01F3
$
Start of command sequence.
01
AcuAir ID code.
F3
Failure Annunciation command Page 3.
CS
Checksum
CR
Carriage Return
RETURNED ANSWER,
Starting
Character
Position
Description of returned data
1
“A” Acknowledge
2
“01” Quantum ID code.
4
Message Code 13
7
Date 13 as mm/dd/yy
15
Time 13 as hh:mm:ss
23
Space
24
Message Code 14
27
Date 14 as mm/dd/yy
35
Time 14 as hh:mm:ss
43
Space
44
Message Code 15
47
Date 15 as mm/dd/yy
55
Time 15 as hh:mm:ss
63
Space
64
Message Code 16
67
Date 16 as mm/dd/yy
75
Time 16 as hh:mm:ss
83
Space
84
Message Code 17
87
Date 17 as mm/dd/yy
95
Time 17 as hh:mm:ss
103
Space
104
Message Code 18
107
Date 18 as mm/dd/yy
115
Time 18 as hh:mm:ss
123
Space
124
CS (Checksum followed by Carriage return,
Line feed. )
CLEAR ALARMS COMMAND: $IDCA
$
Start of command sequence.
ID
AcuAir ID code.
CA
Clear Alarms
CS
Checksum
CR
Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
RETURN Unit Status - Unit data: $01IE
$
Start of command sequence.
01
AcuAir ID code.
IE
Unit Status Command
CS
Checksum
CR
Carriage Return
RETURNED ANSWER,
A
Acknowledge
01
AcuAir ID code.
IE
Unit Status Command
F
Digital Inputs
F
Digital Inputs
F
Digital Outputs
F
Digital Outputs
F
Digital Outputs
F
Digital Outputs
000
Outside/Return Air Dampers
000
Exhaust Command
000
Burner Output
000
Heat Profile
+000
Outside Air Temperature
+000
Discharge Air Temp.
+000
Room/Return Air Temp
+000
Spare Temperature
000
Damper Position
000
Exhaust Fan 1 Position
000
Exhaust Fan 2 Position
00000
Ammonia Detector
000
Humidity
+000
Room Pressure Sensor
+000
Pre-Heat Air Temperature
0
Unit Status: 0-Off; 1-Running; 2-Starting
0
Unit Air Handling Mode:0-Process; 1-Cleanup
0
Unit Control Mode: 0-Local; 1-Remote
0
Control Value: 0-None; 1-Return Air; etc.
0
Control Setpoint: 0-None; 1-Process; etc.
0
Warning: 0-None; 1-Warning; 2-Shutdown
CS
Checksum
CR
Carriage Return
CHANGE STATUS COMMAND: $IDP1
$
Start of command sequence.
ID
AcuAir ID code.
P1
Set Mode to Process 1
CS
Checksum
CR
Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
And 1 “CR”, “LF” if successful.
And 0 “CR”, “LF” if unsuccessful.
CHANGE STATUS COMMAND: $IDP2
$
Start of command sequence.
ID
AcuAir ID code.
P2
Set Mode to Process 2
CS
Checksum
CR
Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
And 1 “CR”, “LF” if successful.
And 0 “CR”, “LF” if unsuccessful.