S90-510 CS (MAR 07)
FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 24
COMMUNICATIONS SETUP
Error detect: BCC / CRC
RTS send delay (20ms): 0
RTS off delay (20ms): 0
Polling mode: Message Based (Do Not Allow
Follower
to initiate messages)
Leader
Message Transmit: Between Station Polls
System (Point-To-Point) additional setup:
Duplicate Detect: OFF
NAK Receive:0
DF1 ENQS:0
(Refer to the Allen-Bradley Programming
Overview Section for more information)
PLC-5 Series and Firmware that support SL C500
commands
Model
Series
Firmware
must
be at least:
C
L
5/30
D
C
A
M
B
J
5/40
C
G
A
M
B
J
C
G
5/60
E
B
READ MESSAGE SETUP EXAMPLE
Instruction Entry for Message Block MG14:0:
Communication Command: SLC Typed Logical
Read
PLC-5 Data Table Address: N9:3
Size in Elements: 20
Local/Remote: Local
Local Node Address: 004 (Quantum™ Panel’s
ID)
Destination Data Table Address: N10:1
Port Number: 0
(Refer to the Allen-Bradley Programming Overview
Section for more information)
Allen-Bradley Programming Overview
This section contains programming examples for reading
data from, and writing data to the Frick
®
Quantum™
control panel from an Allen Bradley (AB) SLC500 or PLC5
processor. AB RSLogix500 programming software has
been used for the following examples, however, these
examples can also be used for the AB RSLogix5 software.
CHANNEL CONFIGURATION
The following are representations of the channel
configuration screens from the AB RSLogix500
programming software for the SLC500. Enter
values as shown in order to establish
communications via AB Protocol.
General Configuration