8.1
Parameter MCC Cold Settings (Self Serve)
MCC Cold SS
Eliwell EWPlus 974 EO
Table of "user" menu paramters
Parameter
Description
Value
Unit
SEt
Temperature Setpoint
1
°C
diF
Compressor relay activation differential
1
°C
HSE
Maximum value that can be assigned to the Setpoint
5
°C
LSE
Minimum value that can be assigned to the Setpoint
-1
°C
dty
Type of defrost (0 = electrical, 1 = reverse cycle, 2 = "Free")
0
num
dit
Interval between the start of two consecutive defrost cycles
3
hours
dEt
Defrost timeout; determines the maximum defrost duration
30
min
dSt
Defrost end temperature (determiend by evaporator probe)
4
°C
FSt
Fan stop temperature
50
°C
Fdt
Fan activation delay after a defrost cycle
0
min
dt
Coil drainage time
0
min
dFd
Allows to select the evaporator probes exclusion during defrost
n
flag
HAL
Maximum temperature alarm
10
°C
LAL
Minimum temperatre alarm
-30
°C
tAO
Temperature alarm signal delay time
30
min
dCS
Deep cooling cycle setpoint
-1
°C
tdC
Deep cooling cycle duration
0
min
OSP
Offset on setpoint
0,5
°C
OdF
Intervention differential correction
4
°C
dnt
Duration of night mode
10
hours
DFt
Duration of fast cooling mode
1
hours
SPn
Night mode setpoint
1
°C
dFn
Night mode offset
2
°C
SPF
Fast cooling setpoint
-1
°C
dFF
Fast cooling offset
0,1
°C
LOC
LOCk Setpoint change shutdown
n
flag
PS1
Password 1
0
num
CA1
Calibration 1 (Pb1)
5
°C
CA2
Calibration 2 (Pb2)
0
°C
CA3
Calibration 3 (Pb3)
0
°C
ddt
Display mode during defrost
2
num
Ldd
Timeout value for display unlick
30
min
H42
Evaporator probe present
y
flag
rEL
firwarme rELease
tAb
tAble of parameters
Table of "installer" menu parameters
Содержание MCC 120
Страница 4: ...Page 4 Service Manual MCC Cold US 20220700...
Страница 20: ...Page 20 Service Manual MCC Cold US 20220700 4 1 Connecting drain or evaporation tray...
Страница 21: ...Service Manual MCC Cold US 20220700 Page 21 4 1 Connecting drain or evaporation tray...
Страница 30: ...Page 30 Service Manual MCC Cold US 20220700 5 1 MCC 90 Drop in Dimensions Self Serve...
Страница 39: ...Service Manual MCC Cold US 20220700 Page 39 6 0 Installation Front door section first version...
Страница 79: ...Service Manual MCC Cold US 20220700 Page 79 11 0 Technical Specifications MCC Cold 2 Full Serve US...
Страница 80: ...Page 80 Service Manual MCC Cold US 20220700 11 1 Technical Specifications MCC Cold 2 Self Serve US...
Страница 81: ...Service Manual MCC Cold US 20220700 Page 81 11 2 Technical Specifications MCC Cold 2 Full Serve US...
Страница 82: ...Page 82 Service Manual MCC Cold US 20220700 11 3 Technical Specifications MCC Cold 3 Full Serve US...
Страница 83: ...Service Manual MCC Cold US 20220700 Page 83...
Страница 84: ...Page 84 Service Manual MCC Cold US 20220700 11 4 Technical Specifications MCC Cold 3 Self Serve US...
Страница 85: ...Service Manual MCC Cold US 20220700 Page 85 11 5 Technical Specifications MCC Cold 4 Full Serve US...
Страница 86: ...Page 86 Service Manual MCC Cold US 20220700 11 6 Technical Specifications MCC Cold 4 Self Serve US...
Страница 87: ...Service Manual MCC Cold US 20220700 Page 87...
Страница 89: ...Service Manual MCC Cold US 20220700 Page 89 Page intentionally left blanc...
Страница 102: ...Page 102 Service Manual MCC Cold US 20220700 13 0 Electrical schematics MCC Cold first version...
Страница 104: ...Page 104 Service Manual MCC Cold US 20220700 13 2 Electrical wiring MCC Cold Self Serve N L...