FR200F series Special Purpose Inverter 

- 45 - 

Average rev 

Average speed Hz*H00.35 

 

H00.39 

 

Roller speed measurement 

0:Calculated  based  on 
speed 
1:Calculated  based  on 
pulse input(DI7) 

 

 

× 

H00.40 

Roller diameter 

0.0~6000.0mm 

50.0mm 

△ 

H00.41 

Roller per revolution 

0~100 

△ 

H00.42 

Current line speed 

0.0~6000.0m/min 

0.0m/min 

⊙ 

 

This function code(H00.39) is used to set the measurement method of roller speed. 

 

0: Calculated based on speed 

 

According to current frequency, estimated the current speed. 

Current line speed(m/min) : 

                    

                      

      

                    

  

    

 

1: Calculated based on pulse input(DI7). 

 

According to practical pulse input, calculated the current Roller speed. 

Current line speed(m/min): 

                    

                 

                     

                    

  

    

 

H00.43 

Completed length 

0~60000m 

0m 

⊙ 

H00.44 

Percent length completed 

0.0~100.0% 

0.0% 

⊙ 

 

H00.43 shows the current completed length. 

 

H00.44 shows the percent length completed: percent = H00.43/(L0+L1+L2….+L15); 

 

Содержание FR200F Series

Страница 1: ...MOUNTING DIMENSIONS AND WEIGHT 3 1 4 PRODUCT TERMINALS CONFIGURATION 6 CHAPTER 2 DEBUGGING GUIDE 11 2 1 SPINNING CONTROL 11 2 2 TWO CONTROL MODES 11 2 3 POWER OFF MEMORY FUNCTION 13 CHAPTER 3 LIST OF...

Страница 2: ...table power type power level and other information FR200F 4T 7 5B Products series Number FR200F Special Purpose Inverter for Textile Machine Input Voltage Level 2 220V 15 30 4 380V 15 30 Input Voltage...

Страница 3: ...92 91 45 60 FR200F 4T 055 85 113 112 55 70 FR200F 4T 075 114 157 150 75 100 FR200F 4T 090 134 160 176 90 125 FR200F 4T 110 160 190 210 110 150 FR200F 4T 132 192 232 253 132 175 FR200F 4T 160 231 282 3...

Страница 4: ...B 198 183 300 287 185 5 5 5 4 FR200F 4T 015B FR200F 4T 018B 255 176 459 443 220 7 15 5 FR200F 4T 022B FR200F 4T 030B FR200F 4T 037 270 130 590 572 260 7 27 5 FR200F 4T 045 FR200F 4T 055 357 230 590 57...

Страница 5: ...nverter 5 H W D W1 D1 Figure 1 5 Landing Installation Diagram Model No Dimensions and wall mounting dimensions mm W W1 H D D1 Mounting Hole Diameter FR200F 4T 450 1200 1036 1900 480 316 14 FR200F 4T 5...

Страница 6: ...and download interfaces Figure 1 6 0 75 2 2kw main circuit terminals diagram b 4 15KW main circuit terminals Control circuit terminals Main circuit terminals Upload and download interfaces PB RFI Fig...

Страница 7: ...terminals Solution 2 diagram d 37 75kw main circuit terminals R L1 U T1 V T2 W T3 POWER MOTOR S L2 T L3 PB Figure 1 10 37 75kW main circuit terminals diagram e 90 280kw main circuit terminals R L1 U...

Страница 8: ...ive has no phase sequence requirement 2 DC bus Terminals and of DC bus have residual voltage after the AC drive is switched off After indicator CHARGE goes off wait at least 10 minutes before touching...

Страница 9: ...rs Maximum output current 200 mA PLC Input terminal of external power supply Connect to 24 V by default When DI1 DI7 need to be driven by external signal PLC needs to be connected to external power su...

Страница 10: ...ly close terminal R2A R2C Normally open terminal R2B R2C Normally close terminal 485 communic ation 485 485 485 communication terminal Rate 4800 9600 19200 38400 57600 115200bps Terminal matching resi...

Страница 11: ...lowing figure shows the principle of spinning control Figure 2 1 Sinning Control Diagram Wirings as below R T U V W M DI1 Run FR200F S Power DI2 Stop DI3 PLC Re set DI4 Fault Re set Running Signal COM...

Страница 12: ...can set the time from current step to next step When running inverter gradually change to next step from current step total consuming time is the set time When PLC running finished inverter will stop...

Страница 13: ...e inverter for textile machine has power off memory function details refer to the function code H00 33 When power off function selection valid inverter can remember the step running before power off a...

Страница 14: ...re listed below Category Parameter Group System Parameters F00 System Parameters Basic Parameters F01 Frequency Command F02 Start Stop Control Start Stop Control F03 Accelerate Decelerate Parameters I...

Страница 15: ...ameter Protection 0 All parameter programmable 0 1 Only F00 02 and this parameter programmable F00 03 G P type display 0 G type constant torque load 0 1 P type variable torque load e g fan and pump F0...

Страница 16: ...d F00 13 Carrier frequency 0 700 16 000kHz Model defined F00 14 Upper carrier frequency 0 700 16 000kHz 8 000kHz F00 15 Lower carrier frequency 0 700 16 000kHz 2 000kHz F00 16 Output voltage 5 0 150 0...

Страница 17: ...igital setting of auxiliary frequency 0 00 Fmax 0 00Hz F01 05 Range of auxiliary frequency 0 Relative to maximum frequency 0 1 Relative to master frequency F01 06 Coeff of auxiliary frequency 0 0 150...

Страница 18: ...Waiting time of stop DC braking 0 0 30 0s 0 0s F02 16 Stop DC braking time 0 0 30 0s 0 0s F02 17 Dynamic brake 0 Disabled 0 1 Enabled 2 Enabled at running 3 Enabled at deceleration F02 18 Dynamic Bra...

Страница 19: ...0 F04 05 Function of terminal DI6 5 JOG reverse 0 F04 06 Function of terminal DI7 6 Coast to stop 0 F04 07 Function of terminal AI1 7 Fault reset RESET 0 F04 08 Function of terminal AI2 8 Running sus...

Страница 20: ...wo wire mode 1 0 1 Two wire mode 2 2 Three wire mode 1 3 Three wire mode 2 F04 16 Terminal UP DOWN frequency adjustment control Unit s place action when stop 001 0 Clear 1 Holding Ten s place action o...

Страница 21: ...Relay 1 output same as unit s place Thousands place Relay 2 output same as unit s place F05 09 Detection width of frequency attained 0 00 20 00Hz 5 00Hz F05 10 FDT1 upper bound 0 00 Fmax 30 00Hz F05 1...

Страница 22: ...of inflection point 2 of curve AI2 25 0 F06 11 Set value corresponding to input of inflection point 1 of curve AI2 100 0 100 0 25 0 F06 12 Input of inflection point 2 of curve AI2 Input of inflection...

Страница 23: ...nput of curve HI 0 00kHz F06 33 Set value corresponding to minimum input of curve HI 100 0 100 0 0 0 F06 34 Maximum input of curve HI Minimum input of curve HI 100 00kHz 50 00kHz F06 35 Set value corr...

Страница 24: ...tual inductance L2 of asynchronous motor 1 0 1 6553 5mH Model defined F08 12 No load current of async motor 1 0 1 1500 0A Model defined F08 13 Field weakening coeff 1 of async motor 1 0 0 100 0 87 F08...

Страница 25: ...V F separation 0 Digital setting F09 16 0 1 keypad potentiometer 2 AI1 3 Multi reference 4 Pulse setting DI7 HI 5 PID 6 AI2 7 AI3 F09 16 Voltage digital setting for V F separation 0 V to rated motor v...

Страница 26: ...me 0 0 6000 0s 0 0s F10 21 Set torque decel time 0 0 6000 0s 0 0s F10 22 Static friction torque compensation 0 0 100 0 5 00 F10 23 Static friction frequency range 0 00 20 00Hz 1 00Hz F10 24 Sliding fr...

Страница 27: ...st to stop 1 Stop according to the stop mode 2 Fault reported but continue to run Ten s place EEPROM read write fault Err15 Same as unit s place Hundred s place Communication overtime error Err18 Same...

Страница 28: ...t Temperature Model defined F11 22 Detection level of power loss 5 0 100 0 20 0 F11 23 Detection time of power loss 0 1 60 0s 5 0s F11 24 Action selection at instantaneous power failure 0 Disabled 1 1...

Страница 29: ...F12 07 Reference 7 100 0 100 0 0 0 F12 08 Reference 8 100 0 100 0 0 0 F12 09 Reference 9 100 0 100 0 0 0 F12 10 Reference 10 100 0 100 0 0 0 F12 11 Reference 11 100 0 100 0 0 0 F12 12 Reference 12 10...

Страница 30: ...6000 0s h 0 0s h F12 29 Running time of step 11 0 0 6000 0s h 0 0s h F12 30 Running time of step 12 0 0 6000 0s h 0 0s h F12 31 Running time of step 13 0 0 6000 0s h 0 0s h F12 32 Running time of ste...

Страница 31: ...en power off 1 Hold when power off 00 Ten s place select if it can be reduced to negative 0 Disable 1 Enable F12 51 UP DOWN speed of Multi reference 0 0 100 0 0 0 Invalid 0 0 Group F13 Process PID F13...

Страница 32: ...Stop integral operation Ten s digit Integral separated 0 Invalid 1 Valid F13 19 PID differential limit 0 0 100 0 0 5 F13 20 PID initial value 0 0 100 0 0 0 F13 21 Holding time of PID initial value 0 0...

Страница 33: ...0 1 6553 5 100 0 F14 07 Command when the length attained 0 Not stop 0 1 Stop F14 08 Set count value 1 65535 1000 F14 09 Designated count value 1 65535 1000 F14 10 Wakeup frequency Dormant frequency F...

Страница 34: ...Run command sources shifted F16 01 Function of STOP RST key 0 STOP RST key valid only when under keypad control 1 1 STOP RST key valid under any run command source F16 02 Keys locked option 0 Not lock...

Страница 35: ...00 00 49 99 03 00 F17 09 User defined Display Parameter 9 00 00 49 99 03 01 F17 10 User defined Display Parameter 10 00 00 49 99 04 00 F17 11 User defined Display Parameter 11 00 00 49 99 04 01 F17 1...

Страница 36: ...0 U00 11 PID feedback 0 60000 0 U00 12 Status of DI1 DI5 digital input terminal DI5 DI4 DI3 DI2 DI1 00000 U00 13 Status of DI6 DI7 digital input terminal DI7 DI6 00 U00 14 Status of digital output te...

Страница 37: ...ication overtime error Err19 PID feedback loss Err20 Continuous running time reached Err21 Parameter upload fault Err22 Parameter download fault Err23 Braking unit fault Err24 Module temperature detec...

Страница 38: ...1 18 Previous 6 categories of faults The same with U01 00 Err00 U01 19 Previous 7 categories of faults The same with U01 00 Err00 U01 20 Previous 8 categories of faults The same with U01 00 Err00 U01...

Страница 39: ...H00 22 Simple PLC 5th step running time length 0 0 6000 0s min m 0 0s min m 4016H H00 23 Simple PLC 6th step running time length 0 0 6000 0s min m 0 0s min m 4017H H00 24 Simple PLC 7th step running t...

Страница 40: ...ev 0 60000RPM 0RPM 4024H H00 37 Average Speed 0 60000RPM 0RPM 4025H H00 38 Average Speed Hz 0 00 600 00Hz 0Hz 4026H H00 39 Roller speed measurement 0 Calculated based on speed 1 Calculated based on pu...

Страница 41: ...0 0s min m H00 22 Simple PLC 5th step running time length 0 0 6000 0s min m 0 0s min m H00 23 Simple PLC 6th step running time length 0 0 6000 0s min m 0 0s min m H00 24 Simple PLC 7th step running t...

Страница 42: ...stop command Ten s place Interrupt operation and then start the selection 0 continue from stop step restart moment Inverter stoped automatically record the current step and then automatically step int...

Страница 43: ...0 Linear mode 0 1 Gradual mode 2 Length mode 0 Linear mode Linear mode when step into a speed timing starts and running to the step setting speed by acce dece time when arrive at the speed inverter co...

Страница 44: ...cy or to pulse input When PLC running finished inverter stops according to the deceleration time running diagram as below 0Hz F1 L0 F2 F3 F4 F5 F6 L1 L2 L3 L4 L5 L6 Output Frequency Hz F7 F8 L7 F9 L8...

Страница 45: ...function code H00 39 is used to set the measurement method of roller speed 0 Calculated based on speed According to current frequency estimated the current speed Current line speed m min 1 Calculated...

Страница 46: ...7 Select an AC drive of higher power class Err02 Dece overcurrent 1 The output circuit is grounded or short circuited 2 The deceleration time is too short 3 The voltage is too low 4 A sudden load is...

Страница 47: ...module is faulty 1 Eliminate external faults 2 Install a reactor or an output filter 3 Check the air filter and the cooling fan 4 Connect all cables properly 5 Contact the agent or 1 Frecon Err09 Inp...

Страница 48: ...unication line is not normal 3 F15 set communication parameters set incorrectly 1 Check the PC Connection 2 Check the communication cable 3 The communication parameters are set correctly Err19 PID fee...

Страница 49: ...rt 3 Manually torque boost or V F curve not appropriate 4 Voltage too low 5 Start the running motor 6 Sudden load in the acce process 7 Model selection of inverter power is too small 1 Troubleshooting...