FR200F series Special Purpose Inverter
- 34 -
4:57600bps
5:115200bps
F15.01
Data format
No check, data format (1-8-N-2) for
RTU
0
×
1: Even parity check, data format
(1-8-E-1) for RTU
2: Odd Parity check, data format
(1-8-O-1) for RTU
3: No check, data format(1-8-N-1)
for RTU
F15.02
Local address
1
~
247 0: Broadcast address
1
×
F15.03
Communication timeout
0.0
~
60.0s
0.0s
×
F15.04
Response time delay
0
~
200ms
1ms
×
F15.05
Master-slave
Communication Mode
0:The inverter is the slave
0
×
1:The inverter is the master
F15.06
The Master
Communication
Sending Data
0: Set frequency
0
×
1: Current running frequency
F15.07
Message
return
when
communication error
0: No return
1: Return
F15.08
U group return value
0:Positive and negative
0
△
1:Absolute value
Group F16 Keys and Display of Keypad Parameters
F16.00
MF.K key setting
0: No function
1
×
1: Jog
2: Forward/reverse switchover
3: Run command sources shifted
F16.01
Function of STOP/RST
key
0: STOP/RST key valid only when
under keypad control
1
×
1: STOP/RST key valid under any
run command source
F16.02
Keys locked option
0: Not locked
0
×
1: Full locked
2: Keys locked other than RUN,
STOP/RST
3: Keys locked other than
STOP/RST
4: Keys locked other than >>
F16.03
LED displayed parameters
setting 1 on running status
0
~
99(correspond U00.00
~
U00.99)
0
△
F16.04
LED displayed parameters
setting 2 on running status
0
~
99(correspond U00.00
~
U00.99)
6
△
F16.05
LED displayed parameters
setting 3 on running status
0
~
99(correspond U00.00
~
U00.99)
3
△
F16.06
LED displayed parameters
setting 4 on running status
0
~
99(correspond U00.00
~
U00.99)
2
△
F16.07
LED displayed parameters
setting 1 on stop status
0
~
99(correspond U00.00
~
U00.99)
1
△
F16.08
LED displayed parameters
setting 2 on stop status
0
~
99(correspond U00.00
~
U00.99)
6
△
F16.09
LED displayed parameters
setting 3 on stop status
0
~
99(correspond U00.00
~
U00.99)
15
△
F16.10
LED displayed parameters
setting 4 on stop status
0
~
99(correspond U00.00
~
U00.99)
16
△