FR200F series Special Purpose Inverter
- 44 -
consuming time is set time. When PLC running finished, inverter stops according to the dece
time, running diagram as below:
0Hz
F0
T0
F1
F2
F3
F4
F5
T1
T2
T3 T4 T5 T6
Output
Frequency
(Hz)
F6
F7
T7
F8
T8 T9
F9
F10
T10
F11
T11
F12
T12
F13
T13
F14
T14
F15
T15
50Hz
Figure 3-3 Gradual mode running diagram
2: Length mode
Frequency gradually changed from current speed to next setting speed, total consuming
length is set length(Length is calculated according to current frequency or to pulse input). When
PLC running finished, inverter stops according to the deceleration time, running diagram as
below:
0Hz
F1
L0
F2
F3
F4
F5
F6
L1
L2
L3 L4 L5 L6
Output
Frequency
(Hz)
F7
F8
L7
F9
L8 L9
F10
F11
L10
F12
L11
F13
L12
F14
L13
F15
L14
F16
L15
50Hz
F0
H00.35
Speed Ratio
0.00
~
600.00RPM/Hz
30.00RP
M/Hz
△
The value use for set external machine ratate speed, which corresponds to inverter 1Hz.
H00.36
Current Rev
0
~
60000RPM
0RPM
⊙
Current rotate speed multiplys H00.35 to get a value for machine rotate speed.
H00.37
Average Rev
0
~
60000RPM
0RPM
⊙
H00.38
Average Speed Hz
0.00
~
600.00Hz
0Hz
⊙
Average speed is the value calculated by every steps frequency and time,
Average speed Hz
=
((F0*T0)+(F1*T1)+…+(F15*T15))/(T0+T1+…+T15)