FR200 Series Vector control inverter
- 29 -
Table 3-1 Requirement of minimum mounting clearances
Drive model
Mounting clearances (mm)
A
B
0.75
~
15kW
≥50
≥100
18.5
~
45kW
≥50
≥200
55kW and above
≥150
≥300
3.3 Fixed manner
a. Wall installation
Wall mounting dimensions refer to Chapter II
(
table 2-3
),
As shown in Fig drilling four holes in
the mounting surface
,
Put the inverter against the panel and mate 4 holes, and then tighten screws in
the 4 holes tighten any of the 2 screws in diagonal position, tighten 4 holes with screws for
strengthened installation.
Hole A
Hole A
Hole A
Hole A
Fig.3-5 Wall mounting
b. Wall mounting
0.75
~
15kW Install the drive mounting bracket as shown in FIG 3-6(a). Wall installation
dimensions refer to Chapter II
(
table 2-4
),
As shown in Fig drilling four holes in the mounting
surface
,
Put the inverter against the panel and mate 4 holes, and then tighten screws in the 4 holes
tighten any of the 2 screws in diagonal position, tighten 4 holes with screws for strengthened
installation.
18.5
~
132kW Install the drive mounting bracket as shown in FIG 3-6(b). Wall installation
dimensions refer to Chapter II
(
table 2-4
),
As shown in Fig drilling four holes in the mounting surface
,
Put the inverter against the panel and mate 4 holes, and then tighten screws in the 4 holes tighten any
of the 2 screws in diagonal position, tighten 4 holes with screws for strengthened installation.