FR200 Series Vector control inverter
- 61 -
F04.16
Terminal UP/DOWN
frequency adjustment
control
Unit's place: action when stop
000
×
0: Clear
1: Holding
Decade: action on power loss
0: Clear
1: Holding
Hundreds place: integral function
0: No integral function
1: Integral function enabled
F04.17
Terminal UP/DOWN
frequency change step
size
0.00
~
50.00Hz 0.00:Disabled
1.00Hz/
200ms
△
F04.18
Terminal action selection
when power on
0
:
Level effective
0
×
1
:
Edge tLevel effective
Group F05 Digital Output
F05.00
Y1 output function
0: No output
1: Drive is running
2: Fault output
3: Frequency-level detection FDT1
output
4: Frequency-level detection FDT2
output
5: Drive in 0Hz running 1(no output
at stop)
6: Drive in 0Hz running 2(output at
stop)
7: Upper limit frequency attained
8: Lower limit frequency attained
9: Frequency attained
10: Inverter is ready to work
11: Drive (motor) overloaded alarm
12: Inverter overheat warning
13: Current running time attained
14: Accumulative power-on time
attained
15: Consecutive running time
attained
16: PLC cycle completed
17: Set count value attained
18: Designated count value
attained
19: Length attained
20: Under load alarm
21:Brake output
1
×
F05.01
Y2 output function
3
F05.02
Relay 1 output function
2
×
F05.03
Relay 2 output function
11
×
F05.04
Y1 output delay time
0.0
~
6000.0s
0.0s
△
F05.05
Y2 output delay time
0.0
~
6000.0s
0.0s
△
F05.06
R1 output delay time
0.0
~
6000.0s
0.0s
△
F05.07
R2 output delay time
0.0
~
6000.0s
0.0s
△
F05.08
Enabled state of digital
output
Unit's place: Y1
0000
×
0: Positive logic
1: Negative logic
Decade: Y2 (same as unit's place)
Hundreds place: Relay 1 output
(same as unit's place)
Thousands place: Relay 2 output
(same as unit's place)