FR200 Series Vector control inverter
- 121 -
Time
Decelerate by
deceleration
time
Accelerate by
acceleration time
Dropping
Time of
Swing
frequency
Jump frequency amplitude
Jump frequency amplitude
Rising Time of
Swing frequency
Swing frequency lower limit
Set frequency Fset
Swing frequency upper limit
Run
command
Swing
frequency
amplitude
Output frequency (Hz)
Figure 6-27
F14.00
Swing frequency setting
mode
Range:0
~
1
Default:0
This parameter is used to select the base value of the swing amplitude.
0: Relative to the central frequency (group F01)
It is variable swing amplitude system. The swing amplitude varies with the central frequency (set
frequency).
1: Relative to the maximum frequency (F01.08maximum output frequency)
It is fixed swing amplitude system. The swing amplitude is fixed.
F14.01
Swing frequency amplitude
Range:0.0
~
100.0%
Default:0.0%
F14.02
Jump frequency amplitude
Range:0.0
~
50.0%
Default:0.0%
This parameter is used to determine the swing amplitude and jump frequency amplitude.
If relative to the central frequency (F14.00 = 0), the actual swing amplitude AW is the calculation
result of group F01 (Frequency source selection) multiplied by F14.01.
If relative to the maximum frequency (F14.00 = 1), the actual swing amplitude AW is the
calculation result of F01.08 (Maximum frequency) multiplied by F14.01.
Jump frequency = Swing amplitude AW x F14.02 (Jump frequency amplitude). If relative to the
central frequency (F14.00= 0), the jump frequency is a variable value.If relative to the maximum
frequency (F14.00= 1), the jump frequency is a fixed value.
The swing frequency is limited by the frequency upper limit and frequency lower limit.
F14.03
Rising Time of Swing
frequency
Range:0.0
~
6000.0s
Default:5.0s
F14.04
Dropping Time of Swing
frequency
Range:0.0
~
6000.0s
Default:5.0s
See Figure 6-26.
F14.05
Set length
Range:0
~
65535m
Default:1000m
F14.06
Number of pulses per meter
Range:0.0
~
6553.5
Default:100.0
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. U00.27 (Actual length) is calculated by
dividing the number of pulses collected by the DI terminal by F14.06 (Number of pulses each meter).
When the actual length U00.27 exceeds the set length in F14.05, the DO terminal allocated with
function (Length reached) becomes ON.During the fixed length control, the length reset operation can
be performed via the DI terminal allocated with function 35. For details, see the descriptions of F04.00
to F04.09.
Allocate corresponding DI terminal with function 34 (Length count input) in applications. If the
pulse frequency is high, DI7/HI must be used.