© FFS 2018 000-1027 r7

Содержание TS-RA1

Страница 1: ...rms Installation Guide franklinfueling com 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 Fax 1 608 838 6433 Tel USA Canada 1 800 225 9787 Tel UK 44 0 1473 243300 Tel Mex 001 800 738 7610 Tel D...

Страница 2: ...s associated systems When no other regulations apply follow NFPA codes 30 30A and 70 from the National Fire Protection Association Failure to follow these codes could result in severe injury death ser...

Страница 3: ...Overfill Alarm and Alarm Acknowledge unit enclosures must be less than 1000 feet away from the 120 VAC electrical power source panel The TS RA1 or TS RA2 Tank Overfill Alarm unit should be mounted ne...

Страница 4: ...NE 1 1 2 1 2 2 2 3 2 4 Figure 3 TS RK Mounting Details Mount the TS RA2 unit through the two 2 mounting holes provided 0 25 DIA 6 4 MM 2 HOLES 5 0 127 mm Figure 4 TS RA2 Mounting Details Wiring the Un...

Страница 5: ...8 OUTPUT 1 9 OUTPUT RETURN 1 3 GROUND 1 4 1 5 REMOTE ALARM SIGNAL ACKN SWITCH LATCH MODE Console Relay Outputs NC1 C1 NO1 NC2 C2 NO2 TS RA1 TS RK 110 VAC LINE 110 VAC NEUT GND EXT ALARM CON To 110 VA...

Страница 6: ...AUD L SW1 1 2 3 4 O N 2AG 3A Fuse Console Relay Outputs TS RK and TS RA2 Wiring Schematic TS RA2 SW1 Switch Position Settings factory settings are shown in bold italic Sound Ouput Level Position 1 Ton...

Страница 7: ...de you select refers to the correct High High or High product threshold You can confirm the units in which the High and High High thresholds are measured under Fuel Management Systems High Product Lim...

Страница 8: ...FFS 2018 000 1027 r7...