background image

Setup and Operation

Set up the console so that the alarms operate properly:

1.  Identify the relay that is being used to activate the overfill alarm equipment. 
2.  Navigate to the setup programming of that relay. 
3.  Confirm that the relay is programmed according to the following: 

•  Name: Overfill Alarm Relay (or similar).

•  Enabled: Yes 

•  Type: Alarm 

•  Polarity: Normal 

•  Logic: OR Logic 

•  Physically Wired As: Normally Open 

•  Number of inputs: 0

NOTE:

 If you have a legacy console, refer to the associated programming manuals for specific information.

4.  Make sure the rule activates the overfill alarm equipment when a HIGH or HIGH HIGH tank alarm occurs. Go to 

the Rules section of programming:

•  Rule:  Overfill Alarm Activate (or similar)

•  Name: Overfill Alarm Activate (or similar)

•  Enabled: Yes 

•  Events 

•  Event: Type Alarm Occurred

•  Category: FMS 

•  Device: Tank 

•  Device ID: Any 

•  Code: High high product level
Actions

•  Action Type: Relay 

•  Module: Power Supply Module 

•  Channel: Overfill Alarm Relay 

•  Action: One Pulse

•  Duration: 2

NOTE:

 Legacy consoles that do not have the One Pulse option must incorporate two seperate actions. One action to 

activate the relay, the second action to deactivate the relay.

NOTE:

 Verify that the code you select sounds the alarm at the correct volume/limit set for each tank. 

NOTE:

 Verify that the code you select refers to the correct High High or High product threshold. You can confirm the units 

in which the High and High High thresholds are measured under Fuel Management Systems/High Product Limit.

5.  Force the tank into the High or High High Alarm by manually raising the product float beyond the threshold and 

confirming the Overfill alarm sounds. Press the acknowledge button on the TS-RK to silence the alarm. 

Testing the Alarm Wiring

Use the following procedure to verify that the tank Overfill Alarm is wired correctly.  If the Setup and Operation procedure 

does not produce an Overfill Alarm, use the following procedure to verify that the issue is not caused by improper wiring.

1.  Go to System/Diagnostic/Relay Status.
2.  Select the Activate/Deactivate checkbox for the Overfill Alarm Relay (or a similar relay). The Active indicator 

becomes GREEN for the associated relay. 

3.  Make sure the Overfill Alarm is activated.

a.  If the Overfill Alarm is activated, the wiring is correct. Clear the Overfill Alarm Relay checkbox to deactivate 

the relay. Press the acknowledgment button on the TS-RK to silence the alarm. 

b.  If the Overfill alarm is not activated, there is an issue with the wiring. Clear the Overfill Alarm Relay checkbox 

to deactivate the relay. Consult the TS-RA1, TS-RA2, TS-RK installation manual for information about proper 

wiring.

NOTE:

 If you have a legacy console, refer to the associated programming manuals for information about manually 

activating relays.

Содержание TS-RA1

Страница 1: ...rms Installation Guide franklinfueling com 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 Fax 1 608 838 6433 Tel USA Canada 1 800 225 9787 Tel UK 44 0 1473 243300 Tel Mex 001 800 738 7610 Tel D...

Страница 2: ...s associated systems When no other regulations apply follow NFPA codes 30 30A and 70 from the National Fire Protection Association Failure to follow these codes could result in severe injury death ser...

Страница 3: ...Overfill Alarm and Alarm Acknowledge unit enclosures must be less than 1000 feet away from the 120 VAC electrical power source panel The TS RA1 or TS RA2 Tank Overfill Alarm unit should be mounted ne...

Страница 4: ...NE 1 1 2 1 2 2 2 3 2 4 Figure 3 TS RK Mounting Details Mount the TS RA2 unit through the two 2 mounting holes provided 0 25 DIA 6 4 MM 2 HOLES 5 0 127 mm Figure 4 TS RA2 Mounting Details Wiring the Un...

Страница 5: ...8 OUTPUT 1 9 OUTPUT RETURN 1 3 GROUND 1 4 1 5 REMOTE ALARM SIGNAL ACKN SWITCH LATCH MODE Console Relay Outputs NC1 C1 NO1 NC2 C2 NO2 TS RA1 TS RK 110 VAC LINE 110 VAC NEUT GND EXT ALARM CON To 110 VA...

Страница 6: ...AUD L SW1 1 2 3 4 O N 2AG 3A Fuse Console Relay Outputs TS RK and TS RA2 Wiring Schematic TS RA2 SW1 Switch Position Settings factory settings are shown in bold italic Sound Ouput Level Position 1 Ton...

Страница 7: ...de you select refers to the correct High High or High product threshold You can confirm the units in which the High and High High thresholds are measured under Fuel Management Systems High Product Lim...

Страница 8: ...FFS 2018 000 1027 r7...

Отзывы: