Содержание EVO 600

Страница 1: ...EVOTM 600AND EVOTM 6000 AUTOMATICTANK GAUGES PROGRAMMING GUIDE ...

Страница 2: ...rom use of this manual or the products We make no warranty of any kind with regard to this material including but not limited to the implied warranties of merchantability and fitness for a particular purpose Copyright 2020 Franklin Fueling Systems LLC Madison WI 53718 All world rights reserved No part of this publication may be stored in a retrieval system transmitted or reproduced in any way incl...

Страница 3: ...ity Control 7 Connecting a PC or Laptop Computer 8 Connecting a PC to the Mini USB Port 8 Connecting a PC to the Ethernet Port 8 Configuring IP Settings for Communication 9 Obtain an IP Address Automatically 9 Use the Following IP Address 10 Check Status of Connection 10 Navigation and Setup 11 Console Navigation 11 Navigation Buttons 11 Quick Jump Menu QJM 11 Quick Jump Menu 12 Login Entry Screen...

Страница 4: ...ptions 23 Programming through FFS PRO Connect Web Interface 23 Settings 24 Configuring 24 System ID 24 System Configuration 24 System Preferences 24 Date Time 25 User Roles 25 Users 25 Address Book 25 Networking 26 Communications 27 Email 28 External Printers 28 Diagnostics 29 Analog Output 29 Discrete Inputs 29 Relays 30 Shifts 30 Fuel Management System 30 Static tank testing 31 Logging 31 Produc...

Страница 5: ...S TPI Overview and Functionality 51 TS TPI Overview 51 On start leveling mode 51 Live Leveling 52 Priority mode 52 Alternating mode 52 Other TS TPI functions 52 TPI Setup 53 Pump Groups 54 Water Separator Overview and Functionality 55 Necessary Components for Operation 55 Programming 56 Water Separator 56 Water Separator Probe 57 Auto Configure Flow Offset Tool 57 Diagnostic Information 59 Alarms ...

Страница 6: ......

Страница 7: ...d must be followed FMS functions The main function of EVO 600 and EVO 6000 ATGs is to represent levels for inventory and tank leak testing by monitoring probe inputs and performing calculations based on those inputs Also Line leak transducers provide line pressure data to perform line leak detection Results from these calculations may be used for system monitoring and or regulatory compliance The ...

Страница 8: ...rt against unsafe practices WARNING This indicates a potentially hazardous situation that could result in severe injury or death if not avoided DANGER This indicates an imminently hazardous situation that will result in death if not avoided This indicates an alarm has activated and provides details so you can correct the problem The system can be custom programmed to perform various actions and se...

Страница 9: ...or harm the environment WARNING Follow all codes that govern how you install and service this product and the entire system Always lock out and tag electrical circuit breakers while installing or servicing this equipment and related equipment A potentially lethal electrical shock hazard and the possibility of an explosion or fire from a spark can result if the electrical circuit breakers are accid...

Страница 10: ...d factory trained technician DANGER Make sure you check the installation location for potential ignition sources such as flames sparks radio waves ionizing radiation and ultrasound sonic waves If you identify any potential ignition sources you must make sure safety measure are implemented Open source software EVO 600 and EVO 6000 ATGs implement open source software released under the General Publi...

Страница 11: ...2 Wire Sensor Module Intrinsically Safe 3WSNS 3 Wire Sensor Module Intrinsically Safe ACIM AC Input Module AIM 4 20mA Analog Input Module Intrinsically Safe AST Aboveground Storage Tank ATG Automatic Tank Gauge CM Controller Module DCE Data Communication Equipment DIM Dispenser Interface Module DTE Data Terminal Equipment DW DWT Double Wall Double Wall Tank FMS Fuel Management Systems IS Intrinsic...

Страница 12: ...n and testing instructions for each type of leak detection sensor are present in the relevant manual and likewise the installation testing and programming of various upgrade kits and optional accessories are also contained in separate manuals addenda or in one of this document s appendices EVO 600 and EVO 6000 Automatic Tank Gauges Installation Guide part number 228180033 EVO 600 and EVO 6000 Auto...

Страница 13: ...screen is an optional feature with EVO 600 and EVO 6000 ATGs This bright display allows easy viewing in any lighting condition Console functions are easily accessed through the LCD screen FFS Pro Connect TheWeb Browser Interface EVO 600 and EVO 6000 ATGs include three methods of establishing a network connection two RJ 45 Ethernet ports a TYPE B Mini USB port or the optional Wi Fi connection These...

Страница 14: ...ing a mini USB cable connect the Mini B Type B connector into the mini USB port on the EVO 600 or EVO 6000 ATG 3 Connect the Type A USB connector to a USB port on the PC 4 If your PC is setup to Obtain an IP address automatically you can open a browser and connect to the EVO 600 or EVO 6000 ATG using https 192 168 171 171 NOTE The first time you connect to an EVO 600 or EVO 6000 via the mini USB p...

Страница 15: ...puter to communicate with EVO 600 and EVO 6000 ATGs These factors depend upon the user s computer knowledge and how the computer is currently configured To determine which method is best for your site read the instructions in the following section carefully Make detailed notes on the current configuration of the TCP IP settings on the PC you are using Read both the Obtain an IP address automatical...

Страница 16: ...he figure may be used to configure the TCP IP settings of your PC 3 Leave the DNS information blank NOTE The consoles default IP address is 192 168 168 168 If the PC is normally configured to Use The Following IP Address make sure that all displayed information is recorded and kept prior to making any changes It may be necessary to use this information to re configure the console once programming ...

Страница 17: ...00 and EVO 6000 ATGs Listed below are buttons that will help you navigate the functions of the console Quick Jump Menu QJM The QJM was developed to simplify system navigation From the QJM you can access sections of the EVO 600 and EVO 6000 ATGs with a few quick selections When the QJM button is selected it will bring you to three tabs Each tab will allow access to different information Application...

Страница 18: ...ng the icon will take you to the summary screen for that item and allow you to access more detailed information Login Entry Screen Save and Enter Password Close Without Saving Password Entry Screen Erase Individual Characters Save and Enter Text Close Without Saving Use Upper Case Characters Adds the com extension to an e mail address ...

Страница 19: ...time you will be prompted to enter an administrative password Create a password and proceed with programming If you accessed the EVO 600 through the Web Interface for the first time the web display will look like this Create a password for administrative level and proceed with interaction with the EVO ...

Страница 20: ...the calibration tool To force the LCD calibration 1 Reboot the ATG 2 Press and hold the LCD screen when the EVO splash screen appears Continue to hold the screen until the calibration tool appears 3 Follow the on screen instructions to complete the calibration process Console Registration Options Each console is custom ordered and built to each customer s specifications That means that all of the ...

Страница 21: ... locate the available printers 5 Locate the desired printer from the list of available printers and click Search in the driver column Programming through the Console Setting Up theATG from the Console From any screen select Quick Jump Menu System Configuration This opens the Setup Menu Configuration Options Using the options in this menu you can change System ID System Configuration System Prefere...

Страница 22: ...ic DHCP to obtain a valid IP address automatically Address This is a logical electronic address like a street address that defines the network address of the console allowing the console to be accessed and to access the network This address will have to match your network if connected to a network in order to talk to a remote communication device or your PC Netmask Masking is a way to diversify th...

Страница 23: ...ess used for e mail functions DHCP Server Dynamic Host Configuration Protocol DHCP is a network protocol that enables a server to automatically assign an IP address to a computer from a defined range of numbers i e a scope configured for a given network See the configuration section for more details NOTE To help prevent network errors do not connect a DHCP server enabled device on a network that a...

Страница 24: ...18 Intentionally Blank ...

Страница 25: ...e using a computer open a web browsing application 2 Type the IP address default is https 192 168 168 168 into the address bar of the browser window To access the console using a remote PC setup communications per the Connecting a PC or Laptop Computer section When using a PC to access console applications through a direct or network connection the EVO 600 or EVO 6000 ATG incorporates a XML eXtens...

Страница 26: ... Files Download Download Selected Backup allows you to download the setup file and store it on any PC connected to the console This file can be uploaded to the console to recover lost settings or copy settings from one site to another 1 Open a web browsing application type the IP address the default IP address is https 192 168 168 168 into the address bar of the browser window 2 The console will n...

Страница 27: ...type the IP address the default IP Address is 192 168 168 168 into the address bar of the browser window The console will navigate to the Home Status page which is customizable in the programming The default Home Page is FMS Tank Status 3 Select Settings Configuration 4 To upload a configuration file click Upload You will be asked to select the file Select the file that you wish to upload NOTE It ...

Страница 28: ...22 Intentionally Blank ...

Страница 29: ...ill see several choices Drag and drop Move or Copy option allows the user to move or copy setup parameters from one programming section to another Download Download Selected Allows users to download sections of the configuration or the entire file Upload Upload a setup file from a computer to a connected ATG Merge Allows users to upload a section or sections of the configuration file thus merging ...

Страница 30: ...hange Once changes are complete select the save button When Confirmation is displayed press Yes to save and apply or No to exit without saving you may press cancel to continue making changes Changes will not be applied until you return to the main menu Refer to the programming tables on the following pages for a more descriptive representation of each option including the submenus of each menu ite...

Страница 31: ...ecific privileges for the role Users The User section allows for individual user account to be created with individual passwords and specific roles to be assigned The system contains one default user admin that has full access to the system Name Enter desired user name Admin requires a password but not a name Password Enter a password for the user Role Select user role Preferences Preferences are ...

Страница 32: ... or Disabled Disabled is the Default DO NOT Select Enabled unless instructed by IT department DHCP Server Start 100 Limit 50 Lease Time 60 min Wi Fi Enabled Yes No Mode Select Access Point for direct connection or infrastructure for network connection Infrastructure allows the system to connect to an existing Wi Fi network Access Point allows other devices to obtain an IP address from and connect ...

Страница 33: ...oose something other than Disabled you also must choose entries for the options that appear RS 485 TPI This can be enabled for the Turbine Pump Interface RS 485 2 This can be configured for External DIM or the Veeder Root Protocol Protocols Veeder Root If you set this to Enabled the Port number is set to 8001 by default You can change this setting if needed Modbus If you set this to Enabled the Po...

Страница 34: ...me From Address your_from address com for example EVO600 at Site 3737 so email will look like From EVO600atSite3737 tanksmtp com From Address Enter IP address of SMTP Host the address of the sender ATG console for example 10 255 1 1 Return address Enter return address for example Return Reply to Jane DoeWorker franklinfueling com Connection Security Select none STARTTLS or SSL TLS Authentication S...

Страница 35: ...gure the outputs for an I O Module The section will only appear if you configure the system with an I O Module available depending on modules loaded in the EVO 600 Name Connection Type IO Module Module Channel Discrete Inputs The Discrete Inputs section allow users to configure any inputs that are discrete in nature either on or off These include the inputs on AC Input Module the Power Supply Modu...

Страница 36: ... corresponding shift length in time will be displayed automatically in equal time for example 3 eight hour shifts Fuel Management System The Fuel Management System section of the configuration is the largest section of setup and allows user to define all of the aspects of the ATG that relate to inventory monitoring tank and line leak detection sensor monitoring and reconciliation Compensation Temp...

Страница 37: ...d Static leak tolerance for testing tanks Yearly Leak Test Threshold Static leak tolerance for testing tanks Confidence Leak testing confidence Choose between 90 95 97 5 99 Please note however 99 is tougher test set lower if having difficult time getting a passing Static Test Minimum Leak Test Time Minimum amount of time 0 8 hours used to test Maximum Leak Test Time Maximum amount of time 1 8 hour...

Страница 38: ...propriate product type Code Enter the code of the product if your company identifies products by using standard Veeder Root protocol code for products in relation to other systems at the site Tank types Click on to add a new tank type then fill in the parameters listed below Name Enter name of tank Capacity Enter volume of tank Shape Physical shape of the tank Select horizontal cylinder vertical c...

Страница 39: ...ensation of tank tilt Float Type Select the type of float s installed on the probe Connection Type Choose if the probe is wired through the probe module or the Multiplexer Sensor Hub Module Select which slot in the EVO the corresponding module is connected to Channel Select the channel where the associated probe is wired SCALD Enable Yes enables SCALD tank testing Qualify Set the minimum required ...

Страница 40: ... is to appear on the Compliance page and in the Regulatory report Members Tank Select tank that is part of the same manifold Tank Select tank that is part of the same manifold Limits Low low Limit Volume percentage Limit Enter the volume that will trigger the Low low Product alarm Low limit Limit Volume percentage Limit Enter the volume that will trigger the Low Product alarm SCALD Enable Yes enab...

Страница 41: ...various Reconciliation differences Complete the onscreen parameters for configuring the alerts Autocalibration if option installed If the Autocalibration feature is installed on the EVO 600 then complete the parameters to autocalibrate the tank chart based on actual product level and volume Compliance tracking Enable Notifications Yes Allows the system to notify user about compliance warnings and ...

Страница 42: ...he pumps that feed the same line into the group External Hooks Hook 1 Select the Input Type for the hook signal to be used for activating and deactivating the pump Input Select the channel to be used to activate and deactivate the pump Corrosion Control if option installed Click on to add a new Water Separator Options to enter Probe Pump and Relay information See Water Separator Overview and Funct...

Страница 43: ... monthly test failures before the pump will be shutdown Annual Tests Enable Select Yes to enable Annual 0 1 gph line tests Wait Period Between Passed Tests Select the number of days the system will wait after a passed test to start another test Shutdown on Test Fail Select Yes to shutdown the pump on a annual Test Failure Fails Before Shutdown Select the number of consecutive annual test failures ...

Страница 44: ... information is displayed Default is 3 Dispenser Volume Can be entered as Gross or Net Gross is not temperature compensated typical US Net is temperature compensated typical Canada Under Dispenser Interface Flow Rate Monitoring Enable Yes No Threshold Flow Rate Under Dispenser Interface Grades and click to add Grades Grade 1 Name Enter given name of grade Include In Vapor Recovery No applies to Ca...

Страница 45: ...ased or Other 1 Based If Internal DIM selected Dispenser Type It refers to the manufacturer of the Dispenser Distribution box Select the type from the drop down list Gilbarco Wayne Tokheim GSite or Bennett515 Some typical examples Gilbarco Universal D Box PA0261 Series Wayne Wayne Dresser D Box GSite Gilbarco MOC G Site and Passport Systems Tokheim M98 M94 Power Center 67 D Boxes Dispenser Communi...

Страница 46: ...nt and back Meter is the number of products dispensed at a fueling point Blended products from forecourt controller is typical Where is data coming from IF POS then blended is just the combination of the two IF coming from Forecourt Controller then separate meter For example Midgrade blend 70 Unleaded 30 Premium If Data from POS then Meter 1 Unleaded Meter 2 Premium If Data from Forecourt controll...

Страница 47: ...ng point After hitting the Query button you will be prompted that Dispense a small amount of product from each hose of this fueling point Make note of what order the grades are dispensed in When done press Configure to finish Sentinel mode Enable this feature of monitoring for theft from the tanks by selecting the Schedule Type from None to Daily or Weekly ...

Страница 48: ...og input is wired Module Select the module number where the analog input is wired Channel Select the channel where the analog input is wired OneTouch Buttons OTB OTBs are customizable programmable touch screen buttons for quick access to EVO functions By setting these up the EVO programmer makes it easy for operators and users to perform daily tasks A maximum of six 6 different buttons can be prog...

Страница 49: ...he condition Type Logic Logic Operator Choose OR or AND Inputs Click to add an Input Input Type Choose the type of input ID Type Choose the device Event Priority Choose the priority of the event Event Code Choose the code of the event Invert Input Choose Yes or No Outputs Click to add a Condition Output Invert Input Choose Yes or No Input Condition Choose the condition for the input Type Choose th...

Страница 50: ...ill trigger the internal relay for a duration of 2 seconds to send a pulse to the external Franklin annunciator This alarm is also stored in the EVO s database Notifications Notifications are Emails Reports and Sounds that are programmable items that the installer programmer can configure the EVO to complete Click to add a Notification ...

Страница 51: ...n that will occur upon event Email Report or sound Content What e mail format is used Content Type E mail Template Text HTML Recipients Chose number of recipients Recipient Address Select address Report Report Type Select report needed Report Device Select device depending or report type Report Action Select email or print Use Default Printer Yes Sound Frequency Enter Freq of sound On Duration Ent...

Страница 52: ...mple is a notification email triggered by a schedule Every day at 5 AM this inventory report will be emailed NOTE Email address is configured in the address book section SMTP server settings is setup in Email section Settings Configuration Email ...

Страница 53: ...e FMP MSH the Multiplexing Sensor Hub reduces the amount of field wiring and cabling from the ATG to the various sensors and probes in the sump See the FMP MSH manual for additional information about installing wiring and compatible components Necessary Components for Operation To function the FMP MSH must connect four wires to an EVO 600 with an RS 485 Module Compatible sensors connecting to the ...

Страница 54: ...e Probes section Select the Module number and channel of the RS 485 Module that the MSH is connected to Then select the Multiplexer Input that the sensor is connected to in the MSH In the example below the LL3 Probe in the Unleaded Tank is connected to Channel number 1 of the Multiplexing Sensor Hub 1 The MSH is connected to the channel number 3 of an RS 485 Module connected in the first slot of a...

Страница 55: ...ors section Select the Module number and channel of the RS 485 Module that the MSH is connected to Then select the Multiplexer Input that the sensor is connected to in the MSH In the example below the CDS 1 sensor is connected to Channel number 4 in the Multiplexing Sensor Hub 1 The MSH is connected to the channel number 1 of an RS 485 Module connected in the first slot of an EVO 600 ...

Страница 56: ...50 Intentionally Blank ...

Страница 57: ...d increases Tank Fuel Management can be used to keep tank levels similar eliminating the need for a syphon system Tank Fuel Management can also be used to pump down one tank to a user defined level and then switch over to the other tank for fuel dispensing In either case there must be at least one submersible pump in each tank TS TPI Overview The TS TPI programming function allows the controllers ...

Страница 58: ...rollers should be set to Main Satellite not Satellite Main Alternating Circuit If the pump controllers are configured for Main Satellite Alternating Circuit the pumps will not turn on in a predicable manner Tanks that are in Leveling or Priority mode are monitored and tested as separate tanks and should NOT be siphoned Alternating mode Alternating mode alternates pumps with each new dispenser sign...

Страница 59: ...tank gauge records a water level that is within 2 of the programmed PUMP HEIGHT measurement the pump will become disabled The tank gauge will indicate a PUMP IN WATER alarm TPI Setup 1 Navigate to Settings Configuration Fuel Management Systems Pumps 2 Click once for each Pump to be installed NOTE To use TPI you must use FE Petro Smart Controllers 3 Set Connection Type to Smart Controller and then ...

Страница 60: ... each Pump Group and configure the group as needed Give a name to the Pump Group select the desired mode identify the pumps or members of the group and identify the external hooks dispenser hook signals associated with that group In the example below Pump 1 and Pump 2 are located in Unleaded Tank 1 and Unleaded Tank 2 The Pump Group is configured to level these two tanks in On start leveling mode ...

Страница 61: ...ending Corrosion Control Water Separator WS System disrupts this microbial activity by removing water from the holding tank Specifically the WS will operate after every fuel delivery to the tank on a programmable scheduled basis and on manual command See the Corrosion Control Installation manual p n 407985002 r1C for additional information about installing the necessary components Necessary Compon...

Страница 62: ...cting and programming in this manner Additional information can be found in the EVO 600 Programming Guide p n 228180061 r1 Water Separator Under Settings Configuration Fuel Management System Corrosion Control you will program the necessary information for the water separator Select to add the separator to the program Create a descriptive name identifying the sump the separator is contained in Next...

Страница 63: ...MP MSH Use the drop down selector and corresponding module and channel options to reflect your installation In our example the probe is connected to Multiplexer Input 2 The FMP MSH is connected to channel 1 of an RS 485 Module in slot 1 located in the EVO 600 ATG Note The water offset should be 0 00 inches but can be field adjusted when the water float is in the bottom position Flow Offset is a pa...

Страница 64: ...the bottom position Selecting this button will take the screen to the configuration screen and automatically populate the Flow Offset reading You may need to scroll down in the program to find it In our example the offset was automatically changed to 0 47 in Next save the program at the top of the configuration page to accept this auto setting ...

Страница 65: ...arator Status From this screen the operator can see if the Water Separator is running the status of the flow sensor the water level status as well as the level in inches The last delivery recorded as well as the last separator start can be seen from this screen Finally two buttons are available the manual Start Water Separator button and the Auto Configure Flow Offset button ...

Страница 66: ...60 Intentionally Blank ...

Страница 67: ...mmed under System Configuration Modules Expected On machines that are in service Check for a flashing green light or no light at all on the 2 Wire Sensor Module and contact FFS Technical Services for support 3 Wire Sensor Module Mismatch Slot 3 Wire Sensor Modules detected does not match the number programmed At startup check that the number of 3 Wire Sensor Modules installed matches the number pr...

Страница 68: ...it will go into a compliance alarm Pass a test or clear the alarm on the device Annual Leak Test Failure Line 0 1 GPH Line leak test failed Follow site policy on line leak procedures Any ANY API volume correction error Tank This error is caused by a programming mistake in the Special Products section Verify Special Product API volume correction program parameters Contact FFS Technical Services Dep...

Страница 69: ...E Density error Tank The density of the product is not within specifications Enter setup and verify the information under density in the probe programming Density float error Tank A communication error has occurred involving the density float Verify programming and contact FFS Technical Services for support DIM Communication Failure DIM_MODULE DIM module number mismatch Slot DIM modules detected d...

Страница 70: ...sue still exists contact Franklin Fueling Systems Technical Services Dept for support Extended Run TPI The STP controller is reporting an extended run condition Refer to the applicable Smart Controller Installation guide for details Failed to Catch Pressure Line The pump OFF pressure has dropped below 7psi within 1 second after the pump was turned off Inspect all sumps for product Refer to LS500 A...

Страница 71: ...ainment Investigate correct High high product level Tank Product level exceeded High High limit set Possible tank overfill condition Acquire an accurate product level If actual product level in tank does not match the consoles displayed current level verify programming is correct High High product volume Tank The specified tank has reached the programmed High High Product Volume Check product volu...

Страница 72: ...m the tank Input bypassed PUMP Internal Error System There is an internal buffer error occurring in the gauge Contact FFS Technical Services for support Internal error contact technical support NONE Invalid Registration None The registration that is loaded is not valid If you have upgraded the site before use the upgrade tool to restore the former registration If you have not upgraded the site bef...

Страница 73: ...locked rotor rating Refer to the applicable Smart Controller Installation guide for details LON module number mismatch Slot Lon Modules detected does not match the number of Lon Modules programmed Check that the number of LON Modules installed matches the number programmed under System Configuration Modules Expected Also check that the Node ID does not conflict with another Node ID in the network ...

Страница 74: ...d Low Product Volume Check product volume and compare to the programmed Low Volume alarm Limit in the setup menu Acquire an accurate product volume and compare to the ATG If levels differ verify programming is correct If alarm persists contact FFS Technical Services for support Manifold Sentinel Mode Alarm MANIFOLD The ATG has detected a theft of fuel during non business hours Verify programming i...

Страница 75: ... not been calibrated Refer to the applicable Smart Controller Installation guide for details Open analog input error TANK Open Circuit TPI The STP controller is reporting an open circuit condition Refer to the applicable Smart Controller Installation guide for details Out of data TANK Over Speed TPI The STP controller is reporting an over speed condition Refer to the applicable Smart Controller In...

Страница 76: ... SENSOR Discriminating Sensor has detected fuel in the containment Locate containment where fuel is present Mitigate issue Troubleshoot the leak Product volume error Tank The Product Volume as reported by the probe has exceeded the limits of the tank Check for proper probe and tank programming at the console If programming is correct inspect the probe to ensure that the float is not stuck in the r...

Страница 77: ...e still exists inspect wiring to probe If the condition still exists contact Franklin Fueling Systems Technical Services for support SCALD manifold test failed MANIFOLD Manifold did not pass Statistical Continuous Automatic Leak Detection Refer to the Tank Testing Section in the Operator s guide for troubleshooting SCALD tank test failed TANK Tank did not pass Statistical Continuous Automatic Leak...

Страница 78: ...ion User s Guide FFS 000 2145 for more information Sump empty SENSOR Sump full SENSOR Discriminating Sensor has detected the containment is full Check containment for collection of fluid Troubleshoot source of the leak Tank delivery detection canceled TANK Tank in service mode TANK Tank product density high limit exceeded TANK Tank product density high limit exceeded Verify programming is set corr...

Страница 79: ... applicable Smart Controller Installation guide for details Under Voltage TPI The STP controller is reporting a voltage level under 200VAC Refer to the applicable Smart Controller Installation guide for details Unexpected reset NONE Unknown NONE Unknown Fault TPI The STP controller is reporting an unknown fault code Check fault condition on Smart controller and contact FFS Technical Services for m...

Страница 80: ... Alarm Warning Device Description Recommended Actions Zero Sales on Fueling Point Alarm RECONCILIATION Zero Sales on Fueling Point Warning RECONCILIATION Zero Sales on Fueling Point Warning Reconciliation ...

Страница 81: ...d ProductsTable Product Name API Gravity 6B Compensation Leaded Regular 63 5 Unleaded Regular 63 5 Unleaded Plus 62 8 Unleaded Extra 62 8 Unleaded Super 51 3 Diesel 32 8 Kerosene 41 8 2 Fuel Oil 32 8 Ethanol 46 1 LPG 146 0 ...

Страница 82: ...76 Intentionally Blank ...

Страница 83: ...Times to Finish 4 000 15 141 65 2 0 hours 6 000 22 712 47 3 0 hours 8 000 30 283 29 4 0 hours 10 000 37 854 12 5 0 hours 12 000 45 424 94 6 0 hours 15 000 56 781 18 7 5 hours 20 000 75 708 24 8 0 hours NOTE Tank sizes are at half capacity NOTE The Leak Threshold value is one half of the Leak Test value ...

Страница 84: ...78 Intentionally Blank ...

Страница 85: ...79 Intentionally Blank ...

Страница 86: ...228180061 r1 ...