INSTALLATION INSTRUCTION MANUAL
TANK DRAWDOWN
5
10. The orange and blue wires are not used. Remove terminals and use electrical
tape to insulate.
11. Re-attach the customer access cover.
12. Re-apply power to the drive.
13. Adjust the pressure setting of the low pressure cut-in switch for the
appropriate off time. The pressure setting on the additional sensor will need to be
set below the regulating sensor, but above the tank pre-charge pressure.
COM
White
Jumper
Low Cut-in Sensor
Regulating Sensor
Pressure
Sensor
Relay
NC NO
Green
Red
Black
Figure 1: SubDrive NEMA 4 Wiring