INSTALLATION INSTRUCTION MANUAL

TANK DRAWDOWN

Tools and Hardware Required

A Philips screwdriver is required to remove the SubDrive access panel. A crimp tool 
may be required for the ¼" quick connects that will attach the aux device to the 
relay interface. 

For the SubDrive Nema 4 units, excluding the SubDrive300, an Auxiliary Relay 
Board is required. An Auxiliary Relay Board kit can be purchased with order 
number 225755901.

Serious or fatal electric shock may result from failure to remove electrical power from 
the SubDrive prior to installing the relay interface. Disconnect power before working on 
the system. Capacitors inside the SubDrive can still hold a lethal voltage for some time 
after power has been removed, so allow 10 minutes after removing supply power for 
dangerous internal voltage to discharge. 

ATTENTION

This equipment is intended for installation only by technically qualified personnel. Failure 
to install it in compliance with national and local electrical codes and within Franklin 
Electric’s recommendations may result in electrical shock or fire hazard, unsatisfactory 
performance, and equipment failure. 

s

 

WARNING

!

1

Purpose

The tank drawdown kit uses the system run relay and an additional pressure sensor 
to allow the use of water stored in the tank during low flow demands.  
 
This setup will allow the drive to control pressure using the regulating sensor to 
maintain constant pressure when operating normally. Once the system shuts off, 
it will use the stored water in the tank until the pressure drops to the secondary 
sensor pressure setting. At that time, the drive will start and regulate to the 
regulating pressure sensor pressure setting. 

E184902

POWER 

CONVERSION 

EQUIPMENT 

4S73

Contents

 

SubDrive NEMA 4  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2-5
SubDrive300  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6-10

Содержание SubDrive NEMA 4

Страница 1: ...SubDrive Tank Drawdown Installation Instruction Manual 225770901...

Страница 2: ...225767101 Rev 2 M1617 10 10 400 E Spring Street Bluffton IN 46714 Tel 260 824 2900 Fax 260 824 2909 www franklin electric com...

Страница 3: ...INSTALLATION INSTRUCTION MANUAL TANK DRAWDOWN...

Страница 4: ...INSTALLATION INSTRUCTION MANUAL TANK DRAWDOWN...

Страница 5: ...ous internal voltage to discharge ATTENTION This equipment is intended for installation only by technically qualified personnel Failure to install it in compliance with national and local electrical c...

Страница 6: ...ve power from the drive and wait at least 10 minutes before accessing the drive to ensure that the bus voltage has been given sufficient time to dissipate 2 Remove the customer access panel ACCESS PAN...

Страница 7: ...harge pressure The pressure can be adjusted once the system is up and running 5 Use the supplied 6 conductor pressure sensor cable to attach the sensor cable to the sensor as shown See Figure 1 pg 5 f...

Страница 8: ...or at J11 8 Connect the Jumper wire to the pressure sensor J11 terminal and to the Common COM terminal of the Auxiliary Relay Board 9 Connect the black wire from the cut in pressure switch to the Norm...

Страница 9: ...Re apply power to the drive 13 Adjust the pressure setting of the low pressure cut in switch for the appropriate off time The pressure setting on the additional sensor will need to be set below the r...

Страница 10: ...etting on the additional sensor will need to be set below the regulating sensor but above the tank pre charge pressure The pressure can be adjusted once the system is up and running 3 Remove the outsi...

Страница 11: ...DRAWDOWN 7 6 Connect the green wire to the pressure sensor J12 terminal at the SubDrive Connect the white wire to the piggyback connector at J12 7 Connect the Jumper wire to the pressure sensor J11 te...

Страница 12: ...om the cut in pressure switch to the Normally Closed NC terminal on the Auxiliary Relay Board Connect the Red wire from the regulating pressure switch to the Normally Open NO terminal on the Auxiliary...

Страница 13: ...the access cover 11 Re apply power 12 Adjust the pressure setting on the low pressure cut in switch for the appropriate off time The pressure setting on the additional sensor will need to be set below...

Страница 14: ...ATION INSTRUCTION MANUAL TANK DRAWDOWN 10 COM White Green Red Jumper Pressure Sensor Relay NC NO Low Cut in Sensor Regulating Sensor Overpressure Sensor Shut Off Blue Orange Black Figure 2 SubDrive300...

Страница 15: ...INSTALLATION INSTRUCTION MANUAL TANK DRAWDOWN Notes...

Страница 16: ...INSTALLATION INSTRUCTION MANUAL TANK DRAWDOWN Notes...