frako PQM 1588 Скачать руководство пользователя страница 3

3

 

7.3.3  Service functions: OPC-UA 

24

 

7.3.4  Service functions: RS-485 

25

  7.3.4.1  RS-485 BUS 1 configuration 

25

  7.3.4.2  RS-485 Bus 2 configuration 

26

 

7.3.5  Service functions: S0 inputs 

26

  7.3.5.1 Configuration 

27

 7.3.5.1.1   Saving the configuration on the PC 

29

 7.3.5.1.2   Loading a saved configuration 

29

7.3.5.1.3   Configuration parameters 

29

7.3.5.1.3.1 General settings 

32

  7.3.5.2  Display of measurement readings 

33

 7.3.5.2.1   Zeroing resettable counters 

35

 

7.3.6  Help: Tools 

35

 8 Operation 

36

 9 Maintenance 

36

 

9.1 Cleaning 

36

 10  Decommissioning and removal, storage and disposal 

37

 

10.1  Decommissioning and removal 

37

 

10.2 Storage 

38

 

10.3 Disposal 

38

 11  General  notes 

39

 12  Scope of supply 

39

Figures and Tables

Figures

Figure 1 

Installation 

11

Figure 2 

PQM connections 

12

Figure 3 

Bus connections 

16

Figure 4  

Digital inputs on PQM1588

     

17

Figure 5 

Opening the web page for the S0 inputs 

18

Figure 6 

Analogue outputs 

18

Figure 7  

IP configuration web pagen

     

22

Figure 8 

Firmware update 

24

Figure 9 

Service functions: OPC-UA 

24

Figure 10 

Service functions: RS-485 

25

Figure 11 

Digital inputs to the PQM 1588 

26

Figure 12 

Configuration of the input at the instrument website 

27

Figure 13 

Instrument web page for configuring the inputs 

28

Figure 14  

Calculation of the parameters from the multiplier for the counter

     

30

Figure 15 

Temperature transducer 

31

Figure 16 

Configuration of the temperature transducer shown above 

31

Figure 17  

Web page for instrument S0 inputs

     

33

Figure 18 

Instrument web page displaying measured values 

33

Tables

Tabelle 3-1 

Description of gateway interfaces 

8

Tabelle 5-1 

Suitable cable types 

16

Tabelle 7-1 

DIP switch functions 

21

Содержание PQM 1588

Страница 1: ...Power Quality Manager PQM 1588 Operating Manual FRAKO Kondensatoren und Anlagenbau www frako com...

Страница 2: ...1 Alarm 1 Relays 15 5 3 2 Alarm 2 Relays 15 5 3 3 OUT 1 to OUT 5 Relays 15 5 4 RS 485 15 5 4 1 RS 485 BUS 1 Modbus RTU 16 5 4 2 RS 485 BUS 2 FRAKO Starkstrombus 17 5 5 Digital inputs 17 5 6 Analogue o...

Страница 3: ...1 Installation 11 Figure 2 PQM connections 12 Figure 3 Bus connections 16 Figure 4 Digital inputs on PQM1588 17 Figure 5 Opening the web page for the S0 inputs 18 Figure 6 Analogue outputs 18 Figure 7...

Страница 4: ...surance Institutions In other countries the equivalent local regulations must be followed Installation commissioning modifications and retrofitting may only be carried out by appropriately qualified p...

Страница 5: ...ly reduced by observing the above safety precautions The user must ensure that all operators are familiarized with this operating manual and follow it at all times This operating manual must be read t...

Страница 6: ...ult in death or serious injury DANGER Indicates an immediate danger of electric shock that if not avoided can result in death or serious injury Notes for the correct functioning of the instrument CAUT...

Страница 7: ...witches DIP switches 8 DIP switches Annunciators LEDs 15 LEDs Design data Dimensions W H D 296mm 260mm 133mm casing Mounting Standard 35mm DIN rail as per EN 50022 Weight approx 0 4kg without packagin...

Страница 8: ...ower Quality Manager collects and records data from the power quality management sys tem Alarms are also detected recorded and forwarded The data acquisition process requires system points which can b...

Страница 9: ...Service functions Ongoing development of the PQM 1588 has endowed this instrument with a growing number of service functions and applications When required these can be enabled at the instrument websi...

Страница 10: ...S 1 configuration If the PQM 1588 is to serve as gateway for the Modbus RTU bus it must not be configured for the data acquisition function Configuration is carried out in SYSTEM SW part of the FRAKON...

Страница 11: ...e instrument base Figure 1 Mounting DANGER To avoid accidents the following must be observed The PQM 1588 must be installed in accordance with its intended use before power is switched on All the conn...

Страница 12: ...power supply voltage exceeds the level specified in this operating manual and stated on the instrument this may cause damage to the PQM 1588 Consequential damage to other parts of the installation is...

Страница 13: ...damage to the PQM 1588 and the electrical installation DANGER To avoid accidents the following must be observed At the PQM 1588 installation site e g control cabinet enclosure all wires and stranded...

Страница 14: ...as specified in this manual The maximum operating voltage across the relay contacts as specified in Section 2 Technical Data When work is carried out on the instrument terminals and connecting cables...

Страница 15: ...rm relay 2 is an NO normally open type Unlike alarm relay 1 it is not bistable During opera tion with no interruptions to the power supply its contacts remain closed In the event of a fault they open...

Страница 16: ...bus RTU Connections are made to the terminals A and B of the connector marked RS 485 BUS 1 A signifies R D T D the Minus signal line B signifies R D T D the Plus signal line signifies chassis signal g...

Страница 17: ...lines no longer than 2m Star topologies can be constructed using an EMB 1101 Repea ter available as an accessory The total length of the bus should not exceed 1200m An EMB 1101 Repeater must be instal...

Страница 18: ...supply the power required for their output signals Figure 6 Analogue outputs The DIP switches 8 and 7 can be set to select the outputs as current or voltage signals Analogue outputs DIP switch OFF ON...

Страница 19: ...above instructions are followed and the precautions specified in Section 1 2 Safety instructions are taken the risk of damaging equipment and assets or endangering life and limb can be significantly r...

Страница 20: ...n and the PQM 1588 started up 6 2 Functional checkout When the power is switched on it takes several seconds before the PQM 1588 starts up This is indicated by all the LEDs lighting up and then after...

Страница 21: ...twork settings Section 7 2 2 can resolve the situation 7 2 1 User network settings Network settings by DHCP In this case the following procedure can be used to determine the IP address IP via DNS The...

Страница 22: ...The instrument website is accessed at the IP address of the PQM 1588 which can be entered in a browser e g http 192 168 0 60 or http pqm snXXXXXX where XXXXXX is the serial number of the instrument w...

Страница 23: ...r the desired second IP address in the appropriate box Enter the associated subnet mask in the appropriate box With this configuration the PQM can be accessed by two different IP networks in the same...

Страница 24: ...firmware is stated against Firmware Release in the table see below Figure 8 Firmware update NOTE The configuration function described in this section 7 3 2 Configuration Firmware update is available f...

Страница 25: ...s by means of drop down menus The Send configuration button must be clicked to complete the process and implement the configuration The PQM 1588 is restarted when necessary 7 3 4 1 RS 485 BUS 1 config...

Страница 26: ...The PQM 1588 has 6 inputs for the reception of pulses or statuses Typical sources of the pulses are a counter with pulse output signal an analogue frequency converter or a volt free contact for signa...

Страница 27: ...PQM S0 counter module This first page shows the momentary condition the momentary derived variable and the non resettable counter total for each individual input The derived variable is calculated fro...

Страница 28: ...clicking the Copy button Note that the entries at Name and Name of derived variable are not copied 4 When all the inputs have been configured the settings must then be transferred to the PQM 1588 by...

Страница 29: ...n then be selected in a file upload dialogue This should normally have the extension JSON but it is not the file name extension that is crucial but its content If it is not a valid configuration file...

Страница 30: ...m as counter units and a pulse value of 1000 pulses per m the multiplier will be 0 001 m per pulse Parameters for derived variable calculation The derived variable calculation is used when a counter o...

Страница 31: ...frequency Value of the measured variable at the transducer s minimum pulse frequency Maximum pulse frequency Upper pulse frequency of the transducer Variable at maximum pulse frequency Value of the m...

Страница 32: ...tory and normally does not need to be changed Counter added to or subtracted from group n The counter reading of each of the 6 inputs can be added to or subtracted from one of the 3 available group co...

Страница 33: ...e Momentary state taking into account input inversion Momentary power flow etc pulses time Non resettable energy counter Figure 17 Web page for instrument S0 inputs To show all the measured values cli...

Страница 34: ...ion figure is arrived at by periodically subtracting the most recently read pulse coun ter total from the momentary total and multiplying the difference by the pulse value Wdiff Counter_Mul Counter_Im...

Страница 35: ...the password which consists of the last four numerals of the PQM 1588 s serial number 4 Click the Send reset command button to execute the reset If the correct password has been entered the message OK...

Страница 36: ...em must be locked out to prevent its being inadvertently switched on again The immediate vicinity must be covered All connections must be checked to verify that they are no longer live Power must not...

Страница 37: ...t be disconnected from the instrument All disconnected cables must be individually isolated and insulated and measures must be taken to prevent their inadvertent contact with live components or electr...

Страница 38: ...red in a clean dry and dust free location The storage temperature must be within the range 20 C to 80 C 10 3 Disposal Any electronic instrument that is no longer required must be disposed of in an env...

Страница 39: ...net as described in Section 4 Mounting the instrument All voltages applied to the instrument must never exceed the limits specified in the technical data The ambient temperatures must always be within...

Страница 40: ...EMS Components Measuring Instruments and Network Analysers Power Quality EMS ISO 50001 FRAKO Kondensatoren und Anlagenbau GmbH Tscheulinstra e 21a D 79331 Teningen Tel 49 7641 453 0 Fax 49 7641 453 5...

Отзывы: