7.3.4.2 RS-485 Bus 2 confi guration
Setting
Description
RS-485 state
Enable or disable the FRAKO Starkstrombus
®
Frakobus address
Bus master address of the PQM 1588
Frakobus max masters
Maximum number of Frakobus masters. Must be the same for all
masters on the bus.
7.3.5 Service functions: S0 inputs
NOTE!
The service function
[7.3.5 service function: S0 inputs]
is available for software
version 2.29.16 or later.
The PQM-1588 has 6 inputs for the reception of pulses or statuses. Typical sources of the pulses
are a counter with pulse output signal, an analogue-frequency converter or a volt-free contact for
signalling the state of a component.
Figure 11
Digital inputs to the PQM 1588
The measurement readings transmitted through the inputs can be acquired via Modbus TCP by
the internal data collector or by another Modbus TCP client (e.g. another PQM 1588).
Register addresses are obtained from the Modbus table for the PQM 1588, which can be down-
loaded as a PDF fi le from the PQM 1588 instrument website at
Help / Downloads
.