7.3.5.1 Configuration
Configuration is carried out at the instrument website.
Figure 12
Configuration of the inputs at
the instrument website
PLEASE NOTE!
After the PQM 1588 is switched on, the web server of the S0 module needs 1 to 2
minutes before it becomes available. The user should therefore allow this time to
elapse before accessing the website. If the website is accessed too early, it may
be necessary to press the F5 key to reload it. Once the system is operating, the
website is available immediately.
To configurate the PQM-S0-Moduls follow this steps:
1. Click
Service functions / S0 inputs
in the navigation pane to display the page for the PQM S0
counter module.
This first page shows the momentary condition, the momentary ‘derived variable’ and the non-
resettable counter total for each individual input. (The derived variable is calculated from the
rate of change of each digital input. Expressed mathematically, it is the derivative with respect
to time of the quantity being metered. Typical examples are electric power demand in kW, flow
rate in litres per hour, manufacturing output in components per hour, or time pulses per hour
from an electricity supplier.)
2. To display the configuration page, click the
Configure S0 inputs
button. Depending on the
browser setting, this page is opened either in a new tab or in a new window.
3. The configuration page thus displayed shows the current settings for the 1st input.
The input to be configured can then be selected from the
S0 input
drop-down menu.