TROUBLE SHOOTING 

FAULT 

POSSIBLE CAUSE 

REMEDY 

Cabinet does not operate/start 

The mains isolating switch on 
the wall, circuit breaker or 
fuses are off at the power 
board 

Turn isolating switch circuit 
breaker or fuses on 

The power switch on the 
cabinet is OFF 

Turn the power switch ON 

The power switch on the unit is 
faulty 

Have the switch replaced 

HA2 Alarm Display on 
Controller 

Compressor discharge pipe 
high temperature 

Turn power off, clean 
condenser radiator & pre-filter. 
Turn power on. 
If no cooling, or alarm returns 
within 24 h, call for service.

 

The cabinet temperature is not 
correct 

One or more rear doors is 
open 

Close the doors and re-test 
temperature after 30 minutes 

Ventilation louvers are blocked  Remove blockages 
Product is blocking air louvers 

Place product on shelves 

Evaporator coil fins are 
blocked 

Remove blockages 

Trays are obstructing air flow 

Re-position trays on shelves 

Thermostat needs adjustment 

Adjust controller 

Ambient temperature > 25

Adjust store air conditioning

 

Evaporator coil iced up 

De-ice coil 

Condenser radiator blocked 

Remove dust and debris 

Thermostat faulty 

Replace controller 

Temperature probe damaged 
or dislocated 

Replace or relocate the 
temperature probe 

Fan not operating 

Check and replace the fan 

The cabinet lights are not 
working 

The light switch is OFF 

Turn the light switch ON 

A LED strip has failed 

Replace the LED assembly 

An LED PSU has failed 

Replace the PSU 

An internal circuit breaker has 
tripped/failed 

Check the wiring and reset 
or replace the circuit breaker 

Doors are not sliding smoothly 

The door is not in its track 

Install the door correctly 

There is debris in the track 

Clean the door tracks 

A door glider is damaged or 
missing 

Have the glider replaced 

Lack of lubrication 

Apply food grade lubricant to 
door tracks

  

External Condensation 

Power supply failed (800 cab.) 

Replace power supply

 

Aluminium parts are corroded 

Damage by caustic detergent  

Order replacement parts 

Service 
Personnel Only 

The table entries in 

italics

 indicate actions to be taken only by qualified Service 

Personnel.  

Содержание IN-5C08-OF

Страница 1: ...Refrigerated Open front Cabinets Curved and Square Formats...

Страница 2: ...Future Products Group Limited All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopy...

Страница 3: ...CABINET Caution Do not store explosive substances such as aerosol cans with flammable propellant in this appliance Mains Supply Cord If the supply cord is damaged it must be replaced by the manufactu...

Страница 4: ...ity Exceptions 8 Specific Exclusions 8 Assessment 8 Time Limit 8 Caution 8 OPERATION 9 Cabinet Layout 9 Self Service Cabinet 9 Shelf Lighting 9 Controls 9 Control Panel 9 Temperature Controller 10 Tem...

Страница 5: ...e Probes 17 Condensate Tray 17 Mandatory Cleaning Routines 18 Warning 18 Removable Filter 18 Condenser Radiator 18 Fault Correction 18 INSTALLATION 19 Regulations 19 Compliance with Local Requirements...

Страница 6: ...24 XR40CX Connections 30 SPECIFICATIONS 31 Mechanical 31 Electrical 31 Controller Setting 32 Dixell XR40CX Settings 32 Compliance 33 Standards 33 Performance Aspects 33 Improvements 33 Ongoing Develo...

Страница 7: ...so that you can receive the full benefits that this cabinet has to offer These instructions cannot however cover all eventualities If you are unsure of any aspect of the installation operation or per...

Страница 8: ...to provide copies of service records in the event of a compressor failure Any damage or malfunction resulting from the use of non FPG supplied spare parts Specific Exclusions The following are specifi...

Страница 9: ...temperature of the cabinet is maintained by a curtain of cold air emitted from a grill below the pelmet of the cabinet The pelmet is heated to avoid external condensation Shelf Lighting All cabinets a...

Страница 10: ...erature inside the cabinet because the refrigeration condenser is controlled in response to the exit air temperature from the evaporator heat exchanger Incorrect adjustment can cause the fins to ice u...

Страница 11: ...switch as shown above The cabinet fans will run and the cabinet temperature will begin to fall The temperature controller is pre set to maintain the cabinet temperature to 2 4 C and should not need a...

Страница 12: ...kept clear of the lightened areas shown in the picture A minimum clearance of 40 mm should be maintained below the shelves and the top air vane The internal air grills at the front and rear of the ca...

Страница 13: ...it is best to clean it at the end of the working day The cabinet will then have time to recover its normal operating temperature before replacing the products Once the cleaning is finished turn the ca...

Страница 14: ...s Thermostat needs adjustment Adjust controller Ambient temperature 25 C Adjust store air conditioning Evaporator coil iced up De ice coil Condenser radiator blocked Remove dust and debris Thermostat...

Страница 15: ...NOT use abrasive pads or cleaners because they will damage the surface of the glass Sliding Doors Sliding glass doors can be removed for cleaning by sliding the door to central position placing hands...

Страница 16: ...abrasive pads or cleaners as these may damage surfaces Warning Dishwasher detergents will damage any anodised aluminium parts Access to the Cabinet Base Cavity Remove the front ticketing rail from th...

Страница 17: ...t and dry vacuum cleaner to suck out the food DO NOT attempt to hose food parts from fins Caution The fins are very sharp Take extra care when cleaning this area Do not bend the fins over as this woul...

Страница 18: ...void the warranty on the refrigeration equipment Removable Filter integral condenser cabinets The removable filter must be kept clean to maintain efficient refrigeration performance Slide the filter o...

Страница 19: ...eparately Site Preparation Ensure the cabinet location and any bench cut outs are made to the precise measurements shown in the Mechanical Drawings Position the cabinet in its allocated working positi...

Страница 20: ...Disposal On the integral condenser versions no drain is required for condensate disposal Check that there is no packing material or debris in the integral condensate boil off tray The element is auto...

Страница 21: ...e is a dc output the LED strip must be replaced Access to LED Strips The LED strips are protected with plastic covers These clip into grooves in the aluminium extrusion Remove the plastic cover to acc...

Страница 22: ...and running components are mounted on the compressor Condenser Radiator Whether integral or remote for efficient refrigeration performance the condenser radiator must be kept clean Failure to do this...

Страница 23: ...ithout water present Fault ACR element is on continuously when no condensate water is present Test Check if the Finder Level Control unit is faulty by disconnecting the probe wire from terminal B1 on...

Страница 24: ...he instrument is fully configurable through special parameters that can be easily programmed through the keyboard XR40CX Compressor Control The regulation is performed according to the temperature mea...

Страница 25: ...To see the min stored temperature in programming mode it browses the parameter codes or decreases the displayed value To switch the instrument off if onF oFF Not enabled To lock unlock the keyboard T...

Страница 26: ...the SET key Press and immediately release the SET key or wait for 5 seconds to display the probe temperature again XR40CX Change the Set point To change the set point value press the SET key for more...

Страница 27: ...1 If no parameter is present in Pr1 after 3s the noP message is displayed Keep the keys pushed till the Pr2 message is displayed NOTE 2 The set value is stored even when the procedure is exited by wai...

Страница 28: ...00 CCt Continuous cycle duration 0 0 24 0h 0 0 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 COn Compressor ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty prob...

Страница 29: ...d Digital input alarm delay 0 255min 5 Nps Number of activation of pressure switch 0 15 15 odc Compress status when open door no Fan CPr F_C no rrd Regulation restart with door open alarm n Y y HES Di...

Страница 30: ...anged CA Serious external alarm i1 F bAL All outputs OFF CA Pressure switch alarm i1 F PAL All outputs OFF XR40CX Alarm Recovery Probe alarms P1 P2 P3 and P4 start some seconds after the fault in the...

Страница 31: ...ont Open Front Number of Shelves Three plus base Three plus base Three plus base Three plus base Display Area 1 1 m2 1 1 m2 1 7 m2 1 7 m2 Refrigerant R449A R449A R449A R449A Refrigerant Mass See Seria...

Страница 32: ...y AC 0 0 0 0 Min Comp On Time Faulty Probe C0n 4 4 4 4 Min Comp Off Time Faulty Probe C0F 6 6 6 6 Min Probe Displayed Lod P4 P4 P4 P4 P1 P2 P3 P4 Defrost Terminate Temp dtE 4 4 4 4 degC Interval Betwe...

Страница 33: ...he equivalent county specific standards including AS NZS CISPR and BS EN 55014 1 Essential safety requirements AS NZS 3820 and AS NZS 4417 Energy efficiency for refrigerated appliances MEPS Australia...

Страница 34: ...34 5000 Series Open Front Cabinets ELECTRICAL CIRCUIT DIAGRAMS Model IN 5C08 OF Curved Inline 5000 Series 800mm Open Front Refrigerated Cabinet Model IN 5C08 OF SQ Square Inline 5000 Series 800mm Open...

Страница 35: ...8 12 OF 35 Future Products Group Model IN 5C12 OF Curved Inline 5000 Series 1200mm Open Front Refrigerated Cabinet Model IN 5C12 OF SQ Square Inline 5000 Series 1200mm Open Front Square Refrigerated C...

Страница 36: ...10522 Polycarbonate Light Cover 1120mm 29405 Polycarbonate Light Cover 720mm 29404 Top Light Replacement Kit for 5C08 Curved 69355 Top Light Replacement Kit for 5C08 Square 69514 Shelf Light Replacem...

Страница 37: ...2480 Front Air Dam 800 cabinet 17652 Front Air Dam 800 square cabinet 25945 Front Air Dam 1200 cabinet 25405 Front Air Dam 1200 square cabinet 27120 Back Outer Sliding Door 800 cabinets 25268 Back Inn...

Страница 38: ...Part No 26126 Rev P September 2019 38 5000 Series Open Front Cabinets MECHANICAL DRAWINGS Cabinet Dimensions REFRIGERATED CABINETS MECHANICAL DRAWINGS IN 5C08 OF...

Страница 39: ...IN 5C08 12 OF 39 Future Products Group IN 5C08 5C12 OF SQ...

Страница 40: ...Part No 26126 Rev A November 2014 40 5000 Series Open Front Cabinets IN 5C12 OF...

Страница 41: ...IN 5C08 12 OF 41 Future Products Group...

Страница 42: ...Part No 26126 Rev A November 2014 42 5000 Series Open Front Cabinets...

Страница 43: ...IN 5C08 12 OF 43 Future Products Group...

Страница 44: ...nually develop improve and support our products Future Products Group Ltd reserves the right to change specifications and design without notice Have a question Please email us at support fpgworld com...

Отзывы: