18
ELECTRIC
Electric setting - Page 1
Electric setting --Page 2
•
Output VOL.:
Selects the output rated voltage.
- The settings available for a HV system are: 208V, 220V, 230V and 240V.
- The settings available for a LV system are: 110V, 115V, 120V and 127V.
• Output FRE.:
Selects the output rated frequency.
-
50Hz:
The output frequency is set at 50Hz.
-
60Hz:
The output frequency is set at 60Hz.
-
AUTO:
If selected, the output frequency will be set according to the value detected the first time the UPS is connected
to the utility. If the input frequency is over 55Hz, the output frequency will be set at 60Hz. If the input frequency is
below 55Hz, then the output frequency will be set at 50Hz.
•
CVCF Mode
(constant voltage and constant frequency function)
-
Enable:
The CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to setting of
the
Output FRE
. The input frequency ranges from 40Hz to 70Hz.
-
Disable:
The CVCF function is disabled. The output frequency will synchronize with the bypass frequency within
45~55 Hz for a 50Hz system or within 55~65 Hz for a 60Hz system. Disable is the default setting.
• Bypass Forbid:
Selects the output rated frequency.
-
Enable:
Bypass forbid is enabled. When selected, operation in Bypass mode is not allowed under any circumstances.
-
Disable:
Bypass forbid is disabled. This is the default setting.