19
Electric setting --Page 3
•
Bypass at UPS off:
Selects the bypass status when manually turning off the UPS. This setting is only available when
Bypass forbid is set to
Disable.
-
Enable:
Bypass enabled. When selected, the bypass mode is active.
-
Disable:
Bypass disabled. When selected, there will be no output through bypass when manually turning off the
UPS.
• Bypass Voltage Range:
Sets the bypass voltage range.
-
L:
Low voltage point for bypass.
- If the UPS is a HV system, the setting ranges from 180V ~ 220V.
- If the UPS is a LV system, the setting ranges from 90V ~ 110V.
-
H:
High voltage point for bypass.
- If the UPS is a HV system, the setting ranges from 230V ~ 264V.
- If the UPS is a LV system, the setting ranges from 120V ~ 140V.
•
Bypass FRE Range:
Sets the bypass frequency range.
The acceptable bypass frequency ranges from 47Hz to 55Hz when the UPS is a 50Hz system, and from 59Hz to 61Hz
when UPS is a 60Hz system.
•
ECO mode:
Enables/Disables the ECO mode. The default setting is
Disable.
•
ECO Voltage Range:
Sets the voltage range for the ECO function.
-
L:
Low voltage point for ECO mode.
- If the UPS is a HV system, this setting ranges from Rated output voltage – 7V to Rated output voltage - 24V.–
22V
is the default setting.
- If the UPS is a LV system, this setting ranges from Rated output voltage – 3V to Rated output voltage - 12V.–
11V
is the default setting.
-
H:
High voltage point for ECO mode.
– If the UPS is a HV system, this setting ranges from Rated output voltage – 7V to Rated output voltage - 24V.–
22V
is the default setting.
– If the UPS is a LV system, this setting ranges from Rated output voltage – 3V to Rated output voltage - 12V.–
11V
is the default setting.