background image

26

4. Troubleshooting guide

If the UPS system does not operate correctly, use the table below to troubleshoot the issue.

Symptom

Possible cause

Solution

Even though the mains supply is 
normal, there are no status indicators 
or alarms.

The AC input cable is not properly 
connected

Check to make sure the power cord 
is firmly connected to an AC wall 
socket

The AC input is connected to the 
UPS outlet

Plug the power cord to a wall socket

Warning code 

0D

 and 

Battery 

disconnect

  are displayed. The 

alarm beeps once every second

The external or internal battery 
connection is incorrect.

Check if all batteries are properly 
connected

Fault code 

27

 and  

Battery too high

 

become illuminated on the LCD 
display, and the alarm starts beeping 
continuously.

Battery voltage is too high or the 
charger fails

Contact your dealer of service center

Fault code

 28

 and  

Battery too low

  

become illuminated on the LCD 
display, and the alarm starts beeping 
continuously.

Battery voltage is too low or the 
charger fails

Please contact your dealer of service 
center

Warning code 

0F

 and 

Overload

 

become illuminated on the LCD 
display, and  the alarm starts 
beeping twice every second

UPS is overloaded

Remove excess loads from UPS 
output

UPS is overloaded. Devices 
connected to the UPS are fed 
directly from utility power via the 
Bypass

Remove excess loads from the UPS 
output

After repetitive overloads, the UPS is 
locked in Bypass mode. Connected 
devices are fed directly from utility 
power.

Remove excess loads from the UPS 
output first. Shut down the UPS 
completely before restarting the unit 
once again

Fault code 

43

 and 

Overload fault

  

become illuminated on the LCD 
display, and the alarm starts beeping 
continuously 

The UPS shuts down automatically 
upon detecting the overload 
condition in the output

Remove excess loads from the UPS 
output and restart the unit once 
again

Fault code 

14

 and 

Inverter short

 

become illuminated,  and the alarm 
starts beeping continuously

The UPS shuts down automatically 
upon detecting the overload 
condition in the output

Check the output wiring and whether 
the connected devices are
short-circuited

Fault codes 

01, 02, 03, 04, 11, 12, 

13, 41

 or 

45

 become illuminated on 

the LCD display, and the alarm starts 
beeping continuously

A UPS internal fault has occurred. 
There are two possible causes:
1. Power is continued to be supplied 
to the load but it is done directly from 
the AC grid via a bypass
2. Power is no longer supplied to the 
load

Please contact the dealer or service 
center

Battery backup time is shorter than 
its nominal value

Batteries are not fully charged

Charge the batteries for at least 5 
hours and then check their capacity. 
If the problem persists, consult your 
dealer

Defective batteries

Contact your dealer for a 
replacement

Содержание FDC-1002T

Страница 1: ...User Manual 3 y ear w arran ty Uninterruptible Power Supply System FDC 1002T FDC 2002T Online UPS...

Страница 2: ...ation 2 1 Unpacking and inspection 2 2 Product overview 2 3 Installation procedure 2 4 UPS connections 2 5 ForzaTracker monitoring software 3 Advanced operation 3 1 Turning the UPS on and off 3 2 Touc...

Страница 3: ...ppliances or equipment that may overload the UPS system such as a laser printer to the output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appli...

Страница 4: ...l de disconnected prior to performing any maintenance or repair inside the unit A battery can present the risk of short circuit current and electrical shock The following precautions should be taken r...

Страница 5: ...fumes and conductive contaminants Do not operate your UPS in an environment where the ambient temperature or humidity is high For best performance keep the indoor temperature between 0 C and 40 C Pla...

Страница 6: ...forzaups com 2 After clicking the software icon choose the required operation system 3 Follow the on screen instructions to install the software 4 When you finished downloading all required files ente...

Страница 7: ...splay the main screen By tapping on the icon on the Home page the five sub menus will come up Control values setting information and data log Touch any of the sub menu icons to enter into the sub scre...

Страница 8: ...bring up the five icons representing five sub menus CONTROL VALUES SETTING INFO DATALOG 3 2 2 Control screen Touch the icon to enter the control sub menu Touch the icon to return to the main interface...

Страница 9: ...main menu inter face Battery test When the UPS is not on test mode Battery Test will appear on the screen Tap on Yes to start Battery testing will come up during the process After a few seconds the b...

Страница 10: ...k if you want to return to the CONTROL screen 3 2 3 Value screen Touch the icon to enter value page To navigate through the menu pages simply tap the or arrows on the screen If you want to return to t...

Страница 11: ...NT Output current in amps BAT VOL Battery voltage in volts VA Output power percentage in VA WATT Output power percentage in watts BUS VOL The real time value of DC BUS P and N voltage MAX TEMPERATURE...

Страница 12: ...menu NOTE Not all settings are available in every operation mode If the setting is not available in the current mode the LCD will keep its original value displayed instead of changing that parameter...

Страница 13: ...s available Buzzer All Mute Enable If selected the alarm will not sound when a related event occurs Disable If selected the alarm of the UPS will go off when a related event occurs Volume Simply touch...

Страница 14: ...t 60Hz If the input frequency is below 55Hz then the output frequency will be set at 50Hz CVCF Mode constant voltage and constant frequency function Enable The CVCF function is enabled The output freq...

Страница 15: ...acceptable frequencies for each system The acceptable bypass frequency ranges from 45Hz to 55Hz when the UPS is a 50Hz system and from 59Hz to 61Hz when UPS is a 60Hz system ECO mode Enables Disables...

Страница 16: ...ted once utility power is restored after the system has been shut down Instead the UPS will be restarted as soon as the battery voltage returns to its adequate level for operation Shutdown Delay Min T...

Страница 17: ...ssword is correct the following screen will come up However if the wrong password is entered then the sys tem will ask the user to make another attempt CAUTION This setting menu is only intended for a...

Страница 18: ...e In this field enter the UPS model Serial Number In this field enter the serial number Company Displays the UPS manufacturer BATT Number Displays total number of installed batteries The UPS should be...

Страница 19: ...eturn to the INITIAL menu page PARAMETERS When you press this option a confirmation window will be displayed as shown in the image above Tap on YES to restore the default values Tap on No to cancel th...

Страница 20: ...ill be set at 60Hz If the input frequency is below 55Hz then the output frequency will be set at 50Hz CVCF Mode constant voltage and constant frequency function Enable The CVCF function is enabled The...

Страница 21: ...pass FRE Range Sets the bypass frequency range The acceptable bypass frequency ranges from 47Hz to 55Hz when the UPS is a 50Hz system and from 59Hz to 61Hz when UPS is a 60Hz system ECO mode Enables D...

Страница 22: ...ected a numeric keypad will come up Enter the time for the duration of the test Click on Enter to initiate the testing process To return to the BAT TEST menu page simply click on the arrow on the bott...

Страница 23: ...o its adequate level Shutdown Delay Min The UPS will shut down after a programmed number of minutes The countdown will start after the dialogue box is confirmed Restore Delay The UPS will automaticall...

Страница 24: ...Information Rated information MCU Version It displays the version of the Microcontroller unit LCD Version It displays the version of the LCD screen integrated in the UPS Serial NO The serial number i...

Страница 25: ...frequency range BYP Voltage Range The acceptable input voltage range for bypass mode BYP FRE Range The acceptable input frequency range for bypass mode ECO VOL Range The acceptable input voltage rang...

Страница 26: ...mber It shows the number of batteries being used Parameter Information Page 3 Datalog Page 3 2 6 Data Log screen Touch the icon to open the data log page The data log is used to record the warning and...

Страница 27: ...INV start fail Fault 12 Inverter voltage is high 12 High INV volt Fault 13 Inverter voltage is low 13 Low INV voltage Fault 14 Inverter is short circuited 14 INV output short Fault 27 Battery voltage...

Страница 28: ...from utility power via the Bypass Remove excess loads from the UPS output After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed directly from utility power Remove exce...

Страница 29: ...fore storing the unit Cover the UPS and place it upright in a cool dry location During storage recharge the battery in accordance with the following table Storage temperature Recharge frecuency Runtim...

Страница 30: ...ange 47 53Hz with a 50Hz system 57 63Hz with a 60Hz system Frequency battery mode 50Hz 0 1Hz or 60Hz 0 1Hz Power factor 0 9 Efficiency AC mode 84 86 Efficiency battery mode 80 82 Overload 105 110 10mi...

Страница 31: ...y 20 90 non condensing Operating altitude Above 1000m the output power decreases 1 every 100m Audible noise 50dB at 1 meter Physical appearance Dimensions 5 7x8 7x11 1in 5 7x8 7x15 6in Weight 22lb 38l...

Страница 32: ......

Отзывы: