28
6. Technical specifications
MPN
FDC-1002T
FDC-2002T
General
Capacity
1000VA/900W
2000VA/1800W
Topology
Double conversion
Input
Nominal voltage
200-240VAC
Voltage range (low line transfer)
180VAC / 160VAC / 140VAC / 120VAC ± 5%
(based on load percentage 100%-80% / 80%-70% / 70%-60% /
60%-0%)
Voltage range (low line comeback)
Low line transfer v 10V
Voltage range (high line transfer)
300VAC ± 5%
Voltage range (high line comeback)
High line transfer voltage - 5V
Frequency
40-70Hz
Power factor
≥0.99 at 100% load
Total harmonic distortion (THDi)
≤10% at 100% load THDU <10%
AC plug style
NEMA 5-15P
Output
Nominal voltage
200/208/220/230/240VAC
AC voltage regulation (battery mode)
± 1%
Frequency (synchronized range)
47-53Hz with a 50Hz system / 57-63Hz with a 60Hz system
Frequency (battery mode)
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Power factor
0.9
Efficiency (AC mode)
≥84%
≥86%
Efficiency (battery mode)
≥80%
≥82%
Overload
105%-110%: 10min / 110%-130%: 30 sec / >130%: 3sec
Transfer time (line to battery)
0ms
Transfer time (inverter to bypass)
4ms
Crest ratio
3:1 (max)
Harmonic distortion
≤3% THD (linear load) / ≤6% THD (non-linear load)
Waveform
Pure sine wave
Total outlets
Three NEMA 5-15R
Four NEMA 5-20R
Battery
Battery type and quantity
12V / 9Ah (2)
12V / 9Ah (4)
Recharge time
4 hours to 90% capacity
Charging current
1A ± 10% (max)
Charging voltage
27.4VDC ± 1%
54.8VDC ± 1%
Communications
LCD display
Integrated 3in LCD touchscreen
Audible
Battery mode: Sounds every 4 seconds Low battery: Sounds every
second Overload: Sounds every 0.5 second
Fault: Continuous sound
Communication ports
SNMP, RS-232, USB
Power management software
ForzaTracker