8
4. OPERATION PRINCIPLE OF THE UPS
The EL 6~10K UPS is a true online UPS employing a double conversion topology. Figure 4.1.1
shows the function block diagram of the UPS system.
4.1 Functional Block Of The UPS
Inverter
I/ P EMI
FILTER
AC
DC
AC I/P
AC O/P
Battery
Battery SW
(Relay & SCR)
Booster
DC
DC
Rectifier
AC
DC
PFC
Battery
Charger
Battery
Charger
DC BUS CAP
Bypass
SCR
O/P EMI
FILTER
MB SW
Controller
Power Supply
(SPS)
Communication
Interface
Ventilation
&
Chassis
Figure 4.1.1 Functional block diagram
*The dashed indicates the interconnection of long backup time model
From logical point of view, the system comprises: An Input/output connector/terminal block, an input
EMI filter, an output EMI filter, a rectifier, a battery switch, a voltage booster, an inverter, an automatic
UPS switch, a maintenance bypass switch, a battery charger, a controller, an auxiliary power supply,
a communication interface, a ventilation module and the chassis.