29
11. Check the wiring and test the UPS.
5.3.1.4 Firmware update
Check the Firmware version with hyper terminal and Q7 command, detail of set the hyper
terminal and method to set a command please refer to previous section, if it is not the
version expected. Replace the CNTL with updated version of firmware.
The procedure of change the control board can be referring to the procedure of replace a
PCB stated in previous section.
5.3.2 Parallel Maintenance Operation
Recommending wiring of parallel operation system shown in figure 5.3.2, figure all of later
explanation are base on this configure.
N
L
JP1
JP2
L1
N 1
L2
N 2
N
L
JP1
JP2
L1
N 1
L2
N 2
To In pu t L in e
To In pu t N eu tral
ou tp ut Li ne
ou tp ut Ne utra l
Figure 5.3.2
Important Note:
If the UPS is used in Single Mode, JP1 and JP2 must be connected by
10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper between JP1 and JP2 must
be removed.