digit number, ranges from 0 to 6, .1 represents about 1V.
INV output rated voltage setting command
Command Format: VXXX < CR >
UPS reply: XXXV
Means: set inverter output rated voltage.
Fault history query command
Command Format: QF < CR >
UPS reply: (KK PPP FF.F OOO EE.E LLL CCC PPP NNN BB.B TT.T
<b7b6b5b4b3b2b1b0><cr>
Meaning: The UPS can record latest fault /Warning code and status of the UPS when the
fault occurs to the UPS. Each word represents different information as follow:
(a) Start byte: (
(b) Fault kind: KK, is the internal fault code for distinguish the type of failure or warning, the
following table shows the code and status represented:
FAULT CODE
Fault Name
Bypass mode
Line mode
Bat mode
Bat test
mode
Eco mode
Bus Fault
:
+BUS Over voltage
$30
$05
$0C
$40
$50
Bus Fault: -BUS Over voltage
$31
$25
$2C
$41
$51
Bus Fault: Bus Unbalance
$32
$15
$1C
$10
$11
Inverter Fault
INV Soft Fail
:
$8D
$04 $0B $42 $52
OP short Fault
$0F
$0F
$0F
$0F
Over Temp Fault
$33
$06
$0A
$43
$53
Overload Fault
$35
$03
$09
$45
$55
Bat SCR Short
$0D
$0D
$0D
$0D
$0D
Communication Fault
$88
$88
$88
$88
$88
Bat Open
$89
$89
Inverter Relay Short
$8B
Parallel Communication Fault
$8E
$8E
$8E
$8E
$8E
Error Model Set
$8F
Par Ups Over Number
$8G
$8G
$8G
$8G
$8G
LoadNegIFault
$8H
$8H
$8H
LoadNegWFault
$8I
$8I
$8I
Warning Code
Bypass mode
Line mode
Bat mode
Bat test mode
Eco mode
Fan Fault
$36
$0G
$2G
$46
$56
Charge Fault
$07
$07
$07
$07
$07
ID Loss
$60
$60
$60
$60
$60
IP Fuse Loss
$70
$70
$70
$70
$70
(c) I/P voltage before fault/warning occurs: PPP.
P represents an integer number ranging from 0 to 9. The unit is Volt.
(d) I/P frequency before fault/warning occurs: FF.F.
F represents an integer number ranging from 0 to 9. The unit is HZ.
(e) Inverter O/P voltage before fault: OOO
O is an integer number ranging from 0 to 9. The unit is Volt.
(f) Inverter O/P frequency before fault: EE.E
E is an integer number ranging from 0 to 9. The unit is HZ.