background image

505 Keystone Rd, Southampton, PA 18966, USA 

(877) 497 6937

.

 [email protected] 

www.fortresspower.com

 

13 

 

Recommended operating parameters of charger/Inverters For 3,000 Cycles: 

• Operating temperature range: 35 F to 120 F (2 °C to 49°C) 

 

Recommended operating parameters of charger/Inverters For 6,000 Cycles: 

• Operating temperature range: 35 F to 110 F (2°C to 43°C) 
• Storage must be equal to or more than twice the rated output of the Inverter 

At the End of Cycle Life capacity is Equivalent to 70% Retained Capacity 

 CAUTION!  Do  Not  Operate  Fortress  Lithium  Batteries  at  an  average  temperature 

exceeding 30 °C / 86 F over the life of the battery.   

8. TROUBLESCHOOTING   

The Battery BMS provides multiple level protection function:   
• Over Charge Voltage Protection 
• Over Discharge Protection 
• Over Current Protection for Discharge Via Thermal Control 
• Short Circuit Protection 
• ON/OFF Switch 

 

In the event of a fault the battery protection circuit will open its internal relay/mosfet disconnecting the 
negative  battery  terminals  form  the  internal  cells.  The  battery  uses  a  relay/mosfet  and  precautions 
should be taken to reduce voltage spikes and large inductance in the application. 

Over Voltage Fault 

62.4±0.4V 

Over Voltage Recovery 

60.8±0.8V 

Low Voltage Fault 

32.0±0.8V 

Low Voltage Recovery 

36.80±1.6V 

If batteries enter a self-protective mode, negligible voltage readings will be present until the unit resets. 
In some instances, after a prolonged shut down, a charge might need to be manually applied to the 
energy storage bank. Should this occur, please contact Fortress Power for technical support. Fortress 
Lithium Batteries are designed to remain robust and safe under most circumstances. 

 

9. SERVICE AND MAINTENANCE   

Batteries  should  be  carefully  inspected  on  a  regular  basis  in  order  to  detect  and  correct  potential 
problems. This routine should be started when the batteries are first received.   

Содержание LFP-10

Страница 1: ...scharge Protection Voltage and Temperature Observation Fortress High performance Lithium Batteries are manufactured at the highest quality standard It comes with large power capacity and a fast charging and continuous discharge power The proprietary architecture and BMS eliminate the need for cooling or ventilation which creates an efficient round trip conversion Fortress Lithium Battery is safe e...

Страница 2: ...ONS 3 1 Technical data 5 4 INSTALLATION 4 1 Tools and material list for installation 6 4 2 Inspection before installation 6 7 4 3 Installation Location 7 4 4 Installation Steps 7 8 4 5 Connection Terminals 8 4 6 Mounting Hardware 8 9 4 7 Final Connection of the Installation 10 5 PARALLEL CONNECTION 10 11 6 Retrofitting 11 7 OPERATING 7 1 Operating environment 11 7 2 Charging 11 12 7 2 1 Charging s...

Страница 3: ...isassemble the battery pack Do not touch the battery pack with wet hands Do not expose the battery pack to moisture or liquids Keep the battery pack away from children and animals Risks of damage to the battery pack Do not allow the battery pack to come into contact with liquids Do not subject the battery pack to high pressures Do not place any objects on top of the battery pack IMPORTANT NOTE Cir...

Страница 4: ... not disassemble or modify the battery If the battery housing is damaged do not touch exposed contents 2 TRANSPORTATION HANDELING AND STORAGE 2 1 Transportation and Handling Do not knock drop puncture or crush battery Do not expose battery to flames incinerate or direct sunlight Do not open battery case or dissemble battery Do not lift battery by the terminal cables Do not vibrate battery Do not e...

Страница 5: ...with flowing water for 15 minutes and seek medical attention Contact with skin Wash the affected area thoroughly with soap and water and seek medical attention Ingestion Induce vomiting and seek medical attention Fire In case of fires make sure that the extinguisher is available near the battery pack If possible move the battery pack to a safe area before it catches fire Note Fire Extinguisher Wat...

Страница 6: ...ithium Batteries are designed for parallel operation only do not arrange in series for increased voltage Series arrangement can result in damage to Fortress Lithium Batteries and will void warranty Do not combine Fortress Power Battery with other brands or chemistries Do not mix different capacity batteries do not mix batteries from different installations or job site 4 1 Tools Materials Insulated...

Страница 7: ...oors Make sure that the installation location meets the following conditions The area is completely waterproof The floor is flat and level Inclination 15 There are no flammable or explosive materials The optimal ambient temperature is within the range from 59 to 95 The temperature and humidity are maintained at a constant level There is minimal dust and dirt in the area IMPORTANT NOTE If the ambie...

Страница 8: ...hand stud resides in a black high temperature insert This connection is for the negative lead 10mm ring terminals along with proper size wiring cables are required to connect battery to inverter charger Do not reverse polarity doing so will void warranty Use a volt meter to check polarity before connecting terminals Water Resistant Plastic Terminal Covers are also included and will be in place whe...

Страница 9: ... the unit is reset In some instances after a prolonged shut down a charge might need to be manually applied to the energy storage bank Should this occur please contact Fortress Power for technical support Fortress Lithium Batteries are designed to remain robust and safe under most circumstances 3 Although each Fortress Lithium Battery contains circuitry that protects the Lithium Ferro Phosphate ce...

Страница 10: ...CTION Fortress Lithium Batteries with the same capacity may be connected in parallel for up to 2 units only All wires should be an appropriate gauge and constructed to handle the loads that will be placed upon it Heavy gauge high strand copper wire is the industry standard due to its stability efficiency and overall quality A qualified installer should understand this and must adhere to the indust...

Страница 11: ...harging Temperature F 4 140 4 140 7 2 Charging Never attempt to charge a battery without first reviewing and understanding the instructions for the charger being used Only use a Fortress Power Approved Lithium Ferro Phosphate LFP charger if ancillary charging is required before installation testing or troubleshooting Failure to use a Fortress Power approved LFP charger will damage the battery and ...

Страница 12: ... and to comply with the Warranty the following guidelines should be followed Understand Charge Stage 1 Bulk Charge Charge at Constant Current CC to Bulk Absorb Voltage 2 Absorption Charge Maintain Constant Bulk Absorb Voltage CV 3 Terminate when charge current drops below 0 05C and 4 Unlike Lead Acid batteries Lithium Ferro Phosphate batteries do not require Float Charge Charger Inverter configura...

Страница 13: ...ircuit Protection ON OFF Switch In the event of a fault the battery protection circuit will open its internal relay mosfet disconnecting the negative battery terminals form the internal cells The battery uses a relay mosfet and precautions should be taken to reduce voltage spikes and large inductance in the application Over Voltage Fault 62 4 0 4V Over Voltage Recovery 60 8 0 8V Low Voltage Fault ...

Страница 14: ...66 USA 877 497 6937 sales fortresspower com www fortresspower com 14 PLEASE CONTACT US FOR TECHNICAL SUPPORT Fortress Power LLC 505 Keystone Road Southampton Pennsylvania 18966 877 497 6937 sales fortresspower com www FortressPower com ...

Отзывы: