7.3 Discharging 

 

Do not discharge battery below operating voltage 

 

Do not discharge battery at rates greater than maximum continuous current 

 

Do not operate in conditions that will exceed the internal operating temperatures of the battery 

7.4 Parameter set up guide in Charger/Inverter   

Before commissioning the energy storage system, the appropriate controller and inverter settings must 
be programmed per the manufacturer’s recommendations. Consult the manufacturer’s manuals and/or 
access technical support (Darfon, Schneider, Outback, SMA, Sol-Ark, Magnum, Outback).   

Although Fortress Lithium batteries  can perform at very high rates and depths of discharge within a 
very wide temperature range, in order to achieve extended life cycles and to comply with the Warranty, 
the following guidelines should be followed: 

Understand Charge Stage 

1) 

Bulk  Charge:  Charge  at  Constant 

Current (CC) to Bulk/Absorb Voltage   
2) 

Absorption  Charge:  Maintain  Constant 

Bulk/Absorb Voltage 

(CV)   

3) 

Terminate  when  charge  current  drops 

below 0.05C and   
4) 

Unlike  Lead  Acid  batteries,  Lithium 

Ferro  Phosphate  batteries  do  not  require 
Float Charge     
 

Charger/Inverter configuration recommendation for best Performance: 

Schneider/outback/ SMA/Sol-Ark 

3000 Cycles 

(90% DoD) 

6000 Cycles 

(80% DoD)

 

Equalized Support   

Off 

Off 

Capacity Limit 

LFP-5:100 Ah   

Equalized Voltage 

Off 

Off 

Recharge Voltage 

51.5V 

Bulk Voltage 

54.6V 

54.4V 

Absorb Voltage 

54.6V 

54.4V 

Low Battery Cut Out Voltage 

50.3V 

50.7V 

High Battery Cut Out Voltage 

61V 

61V 

Float Voltage 

Turn off, if possible

 

54.4V 

Max Charge Current 

80A per battery 

50A per battery 

Max Discharge Current   

80A per battery 

50A per battery 

 

The Battery Parameter Setting Guides with Schneider and Outback Inverters/Chargers are available to 
download on www.fortresspower.com/Resource 

Содержание LFP-10

Страница 1: ...scharge Protection Voltage and Temperature Observation Fortress High performance Lithium Batteries are manufactured at the highest quality standard It comes with large power capacity and a fast charging and continuous discharge power The proprietary architecture and BMS eliminate the need for cooling or ventilation which creates an efficient round trip conversion Fortress Lithium Battery is safe e...

Страница 2: ...ONS 3 1 Technical data 5 4 INSTALLATION 4 1 Tools and material list for installation 6 4 2 Inspection before installation 6 7 4 3 Installation Location 7 4 4 Installation Steps 7 8 4 5 Connection Terminals 8 4 6 Mounting Hardware 8 9 4 7 Final Connection of the Installation 10 5 PARALLEL CONNECTION 10 11 6 Retrofitting 11 7 OPERATING 7 1 Operating environment 11 7 2 Charging 11 12 7 2 1 Charging s...

Страница 3: ...isassemble the battery pack Do not touch the battery pack with wet hands Do not expose the battery pack to moisture or liquids Keep the battery pack away from children and animals Risks of damage to the battery pack Do not allow the battery pack to come into contact with liquids Do not subject the battery pack to high pressures Do not place any objects on top of the battery pack IMPORTANT NOTE Cir...

Страница 4: ... not disassemble or modify the battery If the battery housing is damaged do not touch exposed contents 2 TRANSPORTATION HANDELING AND STORAGE 2 1 Transportation and Handling Do not knock drop puncture or crush battery Do not expose battery to flames incinerate or direct sunlight Do not open battery case or dissemble battery Do not lift battery by the terminal cables Do not vibrate battery Do not e...

Страница 5: ...with flowing water for 15 minutes and seek medical attention Contact with skin Wash the affected area thoroughly with soap and water and seek medical attention Ingestion Induce vomiting and seek medical attention Fire In case of fires make sure that the extinguisher is available near the battery pack If possible move the battery pack to a safe area before it catches fire Note Fire Extinguisher Wat...

Страница 6: ...ithium Batteries are designed for parallel operation only do not arrange in series for increased voltage Series arrangement can result in damage to Fortress Lithium Batteries and will void warranty Do not combine Fortress Power Battery with other brands or chemistries Do not mix different capacity batteries do not mix batteries from different installations or job site 4 1 Tools Materials Insulated...

Страница 7: ...oors Make sure that the installation location meets the following conditions The area is completely waterproof The floor is flat and level Inclination 15 There are no flammable or explosive materials The optimal ambient temperature is within the range from 59 to 95 The temperature and humidity are maintained at a constant level There is minimal dust and dirt in the area IMPORTANT NOTE If the ambie...

Страница 8: ...hand stud resides in a black high temperature insert This connection is for the negative lead 10mm ring terminals along with proper size wiring cables are required to connect battery to inverter charger Do not reverse polarity doing so will void warranty Use a volt meter to check polarity before connecting terminals Water Resistant Plastic Terminal Covers are also included and will be in place whe...

Страница 9: ... the unit is reset In some instances after a prolonged shut down a charge might need to be manually applied to the energy storage bank Should this occur please contact Fortress Power for technical support Fortress Lithium Batteries are designed to remain robust and safe under most circumstances 3 Although each Fortress Lithium Battery contains circuitry that protects the Lithium Ferro Phosphate ce...

Страница 10: ...CTION Fortress Lithium Batteries with the same capacity may be connected in parallel for up to 2 units only All wires should be an appropriate gauge and constructed to handle the loads that will be placed upon it Heavy gauge high strand copper wire is the industry standard due to its stability efficiency and overall quality A qualified installer should understand this and must adhere to the indust...

Страница 11: ...harging Temperature F 4 140 4 140 7 2 Charging Never attempt to charge a battery without first reviewing and understanding the instructions for the charger being used Only use a Fortress Power Approved Lithium Ferro Phosphate LFP charger if ancillary charging is required before installation testing or troubleshooting Failure to use a Fortress Power approved LFP charger will damage the battery and ...

Страница 12: ... and to comply with the Warranty the following guidelines should be followed Understand Charge Stage 1 Bulk Charge Charge at Constant Current CC to Bulk Absorb Voltage 2 Absorption Charge Maintain Constant Bulk Absorb Voltage CV 3 Terminate when charge current drops below 0 05C and 4 Unlike Lead Acid batteries Lithium Ferro Phosphate batteries do not require Float Charge Charger Inverter configura...

Страница 13: ...ircuit Protection ON OFF Switch In the event of a fault the battery protection circuit will open its internal relay mosfet disconnecting the negative battery terminals form the internal cells The battery uses a relay mosfet and precautions should be taken to reduce voltage spikes and large inductance in the application Over Voltage Fault 62 4 0 4V Over Voltage Recovery 60 8 0 8V Low Voltage Fault ...

Страница 14: ...66 USA 877 497 6937 sales fortresspower com www fortresspower com 14 PLEASE CONTACT US FOR TECHNICAL SUPPORT Fortress Power LLC 505 Keystone Road Southampton Pennsylvania 18966 877 497 6937 sales fortresspower com www FortressPower com ...

Отзывы: