5
Systems should be put into storage at 60% SOC and checked monthly to ensure the system SOC does
not fall below 20%. At 20% SOC the battery will self-discharge in approximately 2 months. Also check
the voltage every 3 months and recycle every 6 months if the battery is not use for long time.
2.3 Response to emergency situations
The battery pack comprises multiple batteries that are designed to prevent hazards resulting from
failures. However, Fortress Power cannot guarantee their absolute safety.
❖
Leaking Batteries
If the battery pack leaks electrolyte, avoid contact with the leaking liquid or gas. If one is exposed
to the leaked substance, immediately perform the actions described below.
➢
Inhalation
: Evacuate the contaminated area and seek medical attention.
➢
Contact with eyes
: Rinse eyes with flowing water for 15 minutes and seek medical attention.
➢
Contact with skin
: Wash the affected area thoroughly with soap and water, and seek medical
attention
➢
Ingestion
: Induce vomiting, and seek medical attention
❖
Fire
In case of fires, make sure that the extinguisher is available near the battery pack. If possible,
move
the battery pack to a safe area before it catches fire.
Note:
Fire Extinguisher
Water, carbon dioxide, dry chemical powder and foam are the most effective means to
extinguish a Lithium Ferrous Phosphate (LFP) battery fire
Use ABC Fire extinguisher, if the fire is not from battery and not spread to it yet.
3. PRODUCT INTRODUCTION
3.1 Technical data
Model
LFP-5
Total Energy(kWh)
5.12
Max. Charge Current (Continuous) [A]
80
Max. Discharge Current Continuous) [A]
100
Max Pulse Current for 5sec [A]
180
Capacity [Ah]
100
Voltage [V]
51.2 (48)
Charging Temperature [F]
32~113
Discharging Temperature [F]
-4~140
Dimension [WxDxH]
20x9x26.5
Packaging Dimension [WxDxH]
24x15x32
Connection Terminal
M8
Enclosure Protection Rating
IP 53 (indoor unit)
Weight [Lb]
138
Scalability
Up to 2
Battery DC breaker [A]
125